| Plan Review Notes For Permit 06010881 |
| Permit Number |
06010881 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-30 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT: | | | | | | 1. IF TANK IS BELOW GROUND THE CONTAINER | | | SHALL BE SECURELY ANCHORED PER NFPA 58. | | | (DETAIL REQUIRED) | | | 2. INDICATE SHUT OFF VALVES, AND | | | REGULATORS ON ISOMETRIC DRAWINGS ALSO | | | INDCATE THE MAKE AND MODEL NUMBER OF | | | REGULATORS (ADD TO DRAWINGS) | | | 3. NOTE AS OF OCT. 1ST 2005 FBC-2004 | | | FUEL GAS CODES IN EFFECT. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 |
|