2006-01-30 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. IF TANK IS BELOW GROUND THE CONTAINER
 SHALL BE SECURELY ANCHORED PER NFPA 58.
 (DETAIL REQUIRED)
 2. INDICATE SHUT OFF VALVES, AND
 REGULATORS ON ISOMETRIC DRAWINGS ALSO
 INDCATE THE MAKE AND MODEL NUMBER OF
 REGULATORS (ADD TO DRAWINGS)
 3. NOTE AS OF OCT. 1ST 2005 FBC-2004
 FUEL GAS CODES IN EFFECT.
  
 END OF COMMENTS:
  