| Plan Review Notes For Permit 06010875 |
| Permit Number |
06010875 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-27 00:00:00 | ******DENIED****** | | | | | | 1) WORK AREA SHALL BE ISOLATED SO AS NOT | | | TO INTERUPT ANY REQUIRED BUILDING FIRE | | | PROTECTION EQUIPMENT AND MEANS OF | | | EGRESS. | | | | | | 2) WILL THE DOOR EQUIPED WITH CARD | | | ACCESS EQUIPMENT HAVE ANY IMPACT ON | | | MEANS OF EGRESS? | | | | | | 3) PLEASE INDICATE THE FIRE RATING OF | | | THE DOOR IN TERMS OF MINUTES/HRS. | | | | | | 4) IN ADDITION TO EXIT LIGHTS, PLEASE | | | SHOW LOCATION OF EMERGENCY LIGHTING | | | FACILITIES. | | | | | | 5) AS WITH THE FIRE ALARM SYSTEM, | | | SEPARATE SHOP DRAWINGS AND PERMIT | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|