| 2006-02-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)DECLARE GOVERNING CODE, FBC2004, |
| | MANDATORY EFFECTIVE OCTOBER 1, 2005. |
| | NOTE THAT SHEET M1 STATES FBC2001. |
| | |
| | 3.)PROVIDE A MORE DESCRIPTIVE |
| | SPECIFICATION FOR THE FIRE RATED WALL, |
| | W2-A1.2. |
| | |
| | 4.)IS THIS BUILDING FULLY SPRINKLED? |
| | PROVIDE FIRE SPRINKLER LAYOUT PLAN, |
| | FBC*106.3.5. |
| | |
| | 5.)SPECIFY FIRE RATING FOR THE DOORS |
| | IN ASSEMBLY RATING (HOURS), FBC715.3. |
| | |
| | 6.)SHOW REQUIRED MINIMUM MANEUVERING |
| | CLEARANCE, PULL SIDE, FOR DOOR 12, |
| | FBC11-4.13.6, FBC11 FIGURE 25. |
| | |
| | 7.)THE BREAK ROOM SINK IS TO BE |
| | ACCESSIBLE, FBC11-4.1.1(A).PLEASE |
| | PROVIDE A DETAIL TO SHOW COMPLIANCE WITH |
| | ALL REQUIREMENTS OF 11-4.24, INCLUDING |
| | INDICATING THE REQUIRED CLEAR FLOOR |
| | SPACE ON THE PLAN.NOTE THAT THE WATER |
| | COOLER AS CURRENTLY SHOWN BLOCKS THE |
| | CLEAR FLOOR SPACE.THE CABINET DETAIL |
| | 10-A1.4 DOES NOT COMPLY WITH THE KNEE |
| | CLEARANCE REQUIREMENT OF FBC11-4.24.3. |
| | |
| | 8.)PROVIDE A STRUCTURAL DETAIL FOR THE |
| | ACOUSTICAL CEILING IN CONFORMANCE WITH |
| | ASTM C635, FBC2506.2.1. |
| | |
| | 9.)PROVIDE A STRUCTURAL DETAIL FOR THE |
| | SOFFITS, ASTM C754, FBC2508.1. |
| | |
| | 10.) THE FIRE RESISTANT JOINT SYSTEM |
| | (FIRE RATED WALL) IS TO COMPLY WITH |
| | FBC713.1.PROVIDE AN ASSEMBLY. |
| | |
| | 11.)NO DOOR CLOSERS ARE SHOWN FOR THE |
| | FIRE DOORS; SEE FBC715.3.7. |
| | |
| | |