Plan Review Notes
Plan Review Notes For Permit 06010875
Permit Number 06010875
Review Stop B
Sequence Number 1
Notes
Date Text
2006-02-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE GOVERNING CODE, FBC2004,
 MANDATORY EFFECTIVE OCTOBER 1, 2005.
 NOTE THAT SHEET M1 STATES FBC2001.
  
 3.)PROVIDE A MORE DESCRIPTIVE
 SPECIFICATION FOR THE FIRE RATED WALL,
 W2-A1.2.
  
 4.)IS THIS BUILDING FULLY SPRINKLED?
 PROVIDE FIRE SPRINKLER LAYOUT PLAN,
 FBC*106.3.5.
  
 5.)SPECIFY FIRE RATING FOR THE DOORS
 IN ASSEMBLY RATING (HOURS), FBC715.3.
  
 6.)SHOW REQUIRED MINIMUM MANEUVERING
 CLEARANCE, PULL SIDE, FOR DOOR 12,
 FBC11-4.13.6, FBC11 FIGURE 25.
  
 7.)THE BREAK ROOM SINK IS TO BE
 ACCESSIBLE, FBC11-4.1.1(A).PLEASE
 PROVIDE A DETAIL TO SHOW COMPLIANCE WITH
 ALL REQUIREMENTS OF 11-4.24, INCLUDING
 INDICATING THE REQUIRED CLEAR FLOOR
 SPACE ON THE PLAN.NOTE THAT THE WATER
 COOLER AS CURRENTLY SHOWN BLOCKS THE
 CLEAR FLOOR SPACE.THE CABINET DETAIL
 10-A1.4 DOES NOT COMPLY WITH THE KNEE
 CLEARANCE REQUIREMENT OF FBC11-4.24.3.
  
 8.)PROVIDE A STRUCTURAL DETAIL FOR THE
 ACOUSTICAL CEILING IN CONFORMANCE WITH
 ASTM C635, FBC2506.2.1.
  
 9.)PROVIDE A STRUCTURAL DETAIL FOR THE
 SOFFITS, ASTM C754, FBC2508.1.
  
 10.) THE FIRE RESISTANT JOINT SYSTEM
 (FIRE RATED WALL) IS TO COMPLY WITH
 FBC713.1.PROVIDE AN ASSEMBLY.
  
 11.)NO DOOR CLOSERS ARE SHOWN FOR THE
 FIRE DOORS; SEE FBC715.3.7.
  
  