| 2007-03-15 08:52:02 | ** UNSAT 7TH REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE AS NOTED IN THE PREVIOUS REVIEW, |
| | THE ENERGY CALCULATIONS DO NOT CORRELATE WITH PLANS. |
| | PLEASE SEE THE SQ FT ON THE CALCULATIONS DO NOT |
| | CORRELATE WITH THE SQ FT AS SHOWN ON PLANS. |
| | PLEASE SEE THAT THE SHEET CONTAINING THE LIGHTING HAS |
| | NOW BEEN REVISED HOWEVER NO REVISION TO THE ENERGY |
| | CALCULATIONS WAS DONE TO COORDINATE WITH PLANS AND |
| | FIXTURE LEGEND FOR THE NUMBER OF FIXTURES AND THE |
| | TOTALS ON THE POWER. |
| | PLEASE SEE THE ENERGY CALCULATIONS ON ONE SHEET ARE |
| | DIFFERENT THAN THAT OF THE SAME TOTAL ON ANOTHER |
| | SHEET. |
| | PLEASE SEE THE LIGHTING PLANS MENTIONS NOW THE 4-LAMP |
| | FIXTURES ARE OMITTED, HOWEVER NOTE #3 ON PLANS STILL |
| | INDICATES 4-LAMP FIXTURES ARE TO BE INSTALLED. |
| | PLEASE SEE THE FIXTURE LEGEND WHICH STATES FOR FIXTURE |
| | *L3*,3- 32WATT LAMPS= 85WATTS AS A TOTAL FOR EACH |
| | FIXTURE. THE SAME FOR IS SAID FOR FIXTURE *L2* AND |
| | FIXTURE *L1* WHICH DOES NOT STATE ANY WATTAGE OR |
| | TYPE?? |
| | PLEASE CLARIFY HOW THE FIXTURES CAN CONTAIN 3-32W LAMPS |
| | AND IT ONLY ADDS UP TO 85WATTS OR THE 2-32W AMPS, WHICH |
| | ARE SHOWN @60WATTS? (EFFICIENCY?) |
| | |
| | 2) NOTE: PLEASE KNOW AS PLANS WERE ORIGINALLY SUBMITTED |
| | FOR PLAN REVIEW ONLY, THE FS 553.80(2)(B) DID NOT |
| | APPLY. PLEASE KNOW IF PLANS ARE REJECT FOR THE SAME |
| | COMMENT ON THE FOLLOWING REVIEW, A FEE FOR THE PLAN |
| | REVIEW PORTION OF THE PERMIT FEE WILL BE ASSESSED. |
| | PLEASE ALSO KNOW AT THIS TIME ONE SET OF PLANS AND |
| | ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE |
| | FOR POSSIBLE REVIEW BY THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS. |
| | |
| | 3) NOTE: PLEASE SEE NEW SHEET A1.2 WAS NOT DATED BY THE |
| | ARCHITECT ALONG WITH SHEET T1.1. THIS IS REQUIRED |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. SHEET |
| | A1.2 IS NEW IN SET. |
| | FS 481.221 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |