Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop E
Sequence Number 7
Notes
Date Text
2007-03-15 08:52:02** UNSAT 7TH REVIEW **
  
 1) NOTE: PLEASE SEE AS NOTED IN THE PREVIOUS REVIEW,
 THE ENERGY CALCULATIONS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE THE SQ FT ON THE CALCULATIONS DO NOT
 CORRELATE WITH THE SQ FT AS SHOWN ON PLANS.
 PLEASE SEE THAT THE SHEET CONTAINING THE LIGHTING HAS
 NOW BEEN REVISED HOWEVER NO REVISION TO THE ENERGY
 CALCULATIONS WAS DONE TO COORDINATE WITH PLANS AND
 FIXTURE LEGEND FOR THE NUMBER OF FIXTURES AND THE
 TOTALS ON THE POWER.
 PLEASE SEE THE ENERGY CALCULATIONS ON ONE SHEET ARE
 DIFFERENT THAN THAT OF THE SAME TOTAL ON ANOTHER
 SHEET.
 PLEASE SEE THE LIGHTING PLANS MENTIONS NOW THE 4-LAMP
 FIXTURES ARE OMITTED, HOWEVER NOTE #3 ON PLANS STILL
 INDICATES 4-LAMP FIXTURES ARE TO BE INSTALLED.
 PLEASE SEE THE FIXTURE LEGEND WHICH STATES FOR FIXTURE
 *L3*,3- 32WATT LAMPS= 85WATTS AS A TOTAL FOR EACH
 FIXTURE. THE SAME FOR IS SAID FOR FIXTURE *L2* AND
 FIXTURE *L1* WHICH DOES NOT STATE ANY WATTAGE OR
 TYPE??
 PLEASE CLARIFY HOW THE FIXTURES CAN CONTAIN 3-32W LAMPS
 AND IT ONLY ADDS UP TO 85WATTS OR THE 2-32W AMPS, WHICH
 ARE SHOWN @60WATTS? (EFFICIENCY?)
  
 2) NOTE: PLEASE KNOW AS PLANS WERE ORIGINALLY SUBMITTED
 FOR PLAN REVIEW ONLY, THE FS 553.80(2)(B) DID NOT
 APPLY. PLEASE KNOW IF PLANS ARE REJECT FOR THE SAME
 COMMENT ON THE FOLLOWING REVIEW, A FEE FOR THE PLAN
 REVIEW PORTION OF THE PERMIT FEE WILL BE ASSESSED.
 PLEASE ALSO KNOW AT THIS TIME ONE SET OF PLANS AND
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE
 FOR POSSIBLE REVIEW BY THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
  
 3) NOTE: PLEASE SEE NEW SHEET A1.2 WAS NOT DATED BY THE
 ARCHITECT ALONG WITH SHEET T1.1. THIS IS REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. SHEET
 A1.2 IS NEW IN SET.
 FS 481.221
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]