| 2007-03-02 15:33:49 | ** NOTE ADDED. | | | | | | | | | REPLACED SHEET A1.2 THAT WAS REVISED FOR THE REFLECTED | | | CEILING PLAN NOW CONTAINS A "RUBBER STAMP" FOR THE | | | REQUIRED ORIGINAL SIGNTURE BY THE ARCHITECT PER FS | | | 481.221. INFORMED MR. IAN GUNTHER OF ARCHITECT'S OFFICE | | | THAT WE NEED NEW SIGNED, DATED AND SEALED SHEETS FOR | | | THIS. | | 2007-03-01 11:50:00 | *** UNSAT *** | | | | | | 1) NOTE:PLEASE SEE ENERGY CALCULATIONS HAVE NOW | | | CHANGED WITH THE LIGHTING LOADS. PLEASE SEE THE | | | PREVIOUS DESIGN WAS HIGHER, YET NO CHANGES TO LIGHTING | | | ON PLANS COULD BE FOUND TO DECREASE THIS NUMBER. | | | PLEASE SEE THE NUMBER FOR THE LIGHTING DESIGN NOW | | | EXCEEDS THAT OF THE ALLOWANCE PER 13-415.2.C AND THE | | | TABLES. | | | PLEASE SEE THE ALLOWANCE FOR LIGHTING DENSITIES IS | | | STATED IN THE FBC AS 1.0 PER SQ FT AND YET DESIGN IS | | | NOW SHOWN ABOVE. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|