Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop E
Sequence Number 6
Notes
Date Text
2007-03-02 15:33:49** NOTE ADDED.
  
  
 REPLACED SHEET A1.2 THAT WAS REVISED FOR THE REFLECTED
 CEILING PLAN NOW CONTAINS A "RUBBER STAMP" FOR THE
 REQUIRED ORIGINAL SIGNTURE BY THE ARCHITECT PER FS
 481.221. INFORMED MR. IAN GUNTHER OF ARCHITECT'S OFFICE
 THAT WE NEED NEW SIGNED, DATED AND SEALED SHEETS FOR
 THIS.
2007-03-01 11:50:00*** UNSAT ***
  
 1) NOTE:PLEASE SEE ENERGY CALCULATIONS HAVE NOW
 CHANGED WITH THE LIGHTING LOADS. PLEASE SEE THE
 PREVIOUS DESIGN WAS HIGHER, YET NO CHANGES TO LIGHTING
 ON PLANS COULD BE FOUND TO DECREASE THIS NUMBER.
 PLEASE SEE THE NUMBER FOR THE LIGHTING DESIGN NOW
 EXCEEDS THAT OF THE ALLOWANCE PER 13-415.2.C AND THE
 TABLES.
 PLEASE SEE THE ALLOWANCE FOR LIGHTING DENSITIES IS
 STATED IN THE FBC AS 1.0 PER SQ FT AND YET DESIGN IS
 NOW SHOWN ABOVE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]