| Date |
Text |
| 2007-01-10 07:37:15 | |
| | ** UNSAT *** |
| | |
| | |
| | ** PLEASE SEE PROJECT HAS NOW BEEN CONVERTED TO A |
| | PERMIT. |
| | APIIED DATE FOR PERMIT IS NOW DECEMBER 19TH, 2006. |
| | PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL NEEDS |
| | TO BE ADDRESSED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW. |
| | PLEASE SEE THAT THE TIMES FOR MAXIMUM OVER RIDES TIMES |
| | WERE GIVEN WHICH COME DIRECTLY FROM THE CODE SECTIONS |
| | GIVEN; HOWEVER PLEASE SEE A TIME OF 1HR IS BEING STATED |
| | FOR OCCUPANCY SENSOR TYPES OF DEVICES. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2 AND .1.3. (30MINS MAX |
| | FOR OC SENSOR TYPES AND 4HRS MAXIMUM FOR TIMER TYPE |
| | OVER RIDES. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO |
| | NOT INDICATE THE INFORMATION AS NEEDED TO COMPLY WITH |
| | 13-415.1.AB.1, 13-415.2. |
| | |
| | ** PLEASE SEE THESE NOW INDICATE LIGHTING FOR OPERATING |
| | ROOMS WHICH IF THIS FACILITY HAS "OPERATING ROOM", THEN |
| | THIS ENTIRE PROJECT WOULD FALL UNDER DIFFERENT |
| | REQUIREMENTS IN THE CODE AND WOULD NEED TO RE-DESIGN |
| | ALL ELECTRICAL AS SHOWN FOR SUCH. |
| | |
| | ** PLEASE SEE ENERGY CALCULATIONS NOW DO NOT CONTAIN |
| | ANY WATER HEATING SYSTEMS, WHICH ARE SHOWN ON PLANS, |
| | DOES NOT INCLUDE ANY MECHANICAL A/C SYSTEMS WHICH ARE |
| | SHOWN ON PLANS. |
| | PLEASE SEE OTHER INFORMATION FOR ELECTRICAL SYSTEMS |
| | WHICH ARE ON PLANS NOW ARE REMOVED FROM THE ENERGY |
| | CALCULATIONS. |
| | |
| | |
| | ** PLEASE SEE THE LIGHTING TIMES FOR MAXIMUM PERMITTED |
| | OVER RIDES COULD HAVE BEEN REDLINED ON PLANS, HOWEVER |
| | STATING THIS FACILITY CONTAINS "OPERATING ROOM" ON THE |
| | ENERGY CALCULATIONS WHEN THIS DOES NOT HAVE THIS |
| | OCCUPANCY AS A HOSPITAL. |
| | |
| | |
| | ** PLEASE KNOW ONE COPY OF ENERGY CALCULATIONS |
| | SUBMITTED AND PLANS ARE NOW BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | |
| | |
| | 2) NOTE: PLEASE SEE PERMIT APPLICATION NOW CONTAINS A |
| | PARCEL CONTROL NUMBER WHICH IS FOR THE ADDRESS OF 3230, |
| | THIS WILL BE CHANGED BY THE ADDRESSING REVIEWER OR THIS |
| | OFFICE BEFORE PERMIT ISSUANCE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-09 18:27:13 | IN ELEC FOR REVIEW |