Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop E
Sequence Number 5
Notes
Date Text
2007-01-10 07:37:15 
 ** UNSAT ***
  
  
 ** PLEASE SEE PROJECT HAS NOW BEEN CONVERTED TO A
 PERMIT.
 APIIED DATE FOR PERMIT IS NOW DECEMBER 19TH, 2006.
 PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL NEEDS
 TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW.
 PLEASE SEE THAT THE TIMES FOR MAXIMUM OVER RIDES TIMES
 WERE GIVEN WHICH COME DIRECTLY FROM THE CODE SECTIONS
 GIVEN; HOWEVER PLEASE SEE A TIME OF 1HR IS BEING STATED
 FOR OCCUPANCY SENSOR TYPES OF DEVICES.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2 AND .1.3. (30MINS MAX
 FOR OC SENSOR TYPES AND 4HRS MAXIMUM FOR TIMER TYPE
 OVER RIDES.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO
 NOT INDICATE THE INFORMATION AS NEEDED TO COMPLY WITH
 13-415.1.AB.1, 13-415.2.
  
 ** PLEASE SEE THESE NOW INDICATE LIGHTING FOR OPERATING
 ROOMS WHICH IF THIS FACILITY HAS "OPERATING ROOM", THEN
 THIS ENTIRE PROJECT WOULD FALL UNDER DIFFERENT
 REQUIREMENTS IN THE CODE AND WOULD NEED TO RE-DESIGN
 ALL ELECTRICAL AS SHOWN FOR SUCH.
  
 ** PLEASE SEE ENERGY CALCULATIONS NOW DO NOT CONTAIN
 ANY WATER HEATING SYSTEMS, WHICH ARE SHOWN ON PLANS,
 DOES NOT INCLUDE ANY MECHANICAL A/C SYSTEMS WHICH ARE
 SHOWN ON PLANS.
 PLEASE SEE OTHER INFORMATION FOR ELECTRICAL SYSTEMS
 WHICH ARE ON PLANS NOW ARE REMOVED FROM THE ENERGY
 CALCULATIONS.
  
  
 ** PLEASE SEE THE LIGHTING TIMES FOR MAXIMUM PERMITTED
 OVER RIDES COULD HAVE BEEN REDLINED ON PLANS, HOWEVER
 STATING THIS FACILITY CONTAINS "OPERATING ROOM" ON THE
 ENERGY CALCULATIONS WHEN THIS DOES NOT HAVE THIS
 OCCUPANCY AS A HOSPITAL.
  
  
 ** PLEASE KNOW ONE COPY OF ENERGY CALCULATIONS
 SUBMITTED AND PLANS ARE NOW BEING RETAINED BY THIS
 OFFICE.
  
  
  
 2) NOTE: PLEASE SEE PERMIT APPLICATION NOW CONTAINS A
 PARCEL CONTROL NUMBER WHICH IS FOR THE ADDRESS OF 3230,
 THIS WILL BE CHANGED BY THE ADDRESSING REVIEWER OR THIS
 OFFICE BEFORE PERMIT ISSUANCE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-09 18:27:13IN ELEC FOR REVIEW


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved