2006-11-04 18:36:28*** UNSAT 4TH REVIEW***
  
  
 ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY.
 NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE.
 PLEASE KNOW A CODE CHANGE FOR NFPA-70 IS COMING AND IF
 PERMIT IS NOT APPLIED FOR BEFORE STATE ADOPTS NEW CODE,
 THEN THE PLANS WILL BE REQUIRED TO CHANGE AS NEEDED.
 THE TENTATIVE DATE IS DEC 1ST, 2006
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND
 ENERGY CALCULATIONS IN AND NEAT AND ORDERLY FASHION.
 PLEASE SEE ONLY PARTS OF WHAT SEEMS TO BE A PARTIAL SET
 OF REVISED ENERGY CALCULATIONS WERE SUBMITTED. PLEASE
 SEE IN EITHER CASE THE PARTIAL ENERGY CALCULATIONS ARE
 NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF
 RECORD??? THEY ARESIGNED AND DATED10/23/06, BUT NOT
 SEALED AND NOT IN ANY ORDER OF ANY KIND??
 PLEASE SUBMIT AS REQUIRED AND REQUESTED.
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH 106.1.2, 106.1.3. , 106.3.5.1 ETC.
  
  
 2) NOTE: PLEASE SEE OUR SYSTEM STILL INDICATES PLANS
 BEING REVIEWED UNDER THE ADDRESS OF 3222 COMMERCE PL,
 THE "PLAN REVIEW" SUBMITTAL SHEET WHEN PLANS WERE
 SUBMITTED ALSO INDICATE "3222"
 PLEASE CORRELATE, AND ONCE AN ADDRESS IS FINALIZED,
 PLEASE ADJUST PLANS AS NEEDED OR IF NEEDED.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 HAS NOT YET BEEN MET. PLEASE SEE
 NEW OC SENSOR TYPE SWITCHES WERE ADDED TO SOME ROOMS
 AND SOME AREAS INDICATE A NOTE #7 IN AN OCTAGONAL SHAPE
 WHICH MENTIONS TO ADD AN OVER RIDE SWITCH, WITH A MAX
 OF 1HR, HOWEVER PLEASE SEE THIS NOTE IS ADDED AT FRONT
 DOOR, YET NO "S" IS SHOWN? PLEASE SEE OTHER AREAS WHICH
 DO INDICATE AN OC, YET NO TIME LIMITS ARE INDICATED ON
 SYMBOL LEGEND?
 PLEASE SEE OTHER AREAS WHICH CONTAIN SWITCHES, BUT THEY
 WERE NOT CHANGED???
 PLEASE SEE MAX TIMES PERMITTED ON OC SENSOR DEVICES AS
 PERVIOUSLY NOTED PER SECTIONS GIVEN. (30MINS MAX ON OC
 TYPE AND 4HR MAX ON TIMER TYPE)
 PLEASE SEE NOTES #1 , AS ENERGU
 CALCULATIONS/PERFORMANCE CALCUALTIONS SUBMITTED DO NOT
 PROVIDE THE INFORMATION AS REQUIRED. PLEASE SEE
 13-415.2.ABC.1, TABLE(S) 415.2.C.1
  
 4) NOTE: PLEASE SEE A SIGN CIRCUIT HAS NOW BEEN ADDED,
 YET PLEASE SEE 600.5, WHICH REFERENCES THE
 220.3(B)(6). PLEASE SEE THE MINIMUM VA SHALL BE
 INDICATED. (SHOWN AS 600VA)
  
  
 ** PLEASE KNOW, AS PLANS HAVE ONLY BEEN SUBMITTED FOR A
 "PLAN REVIEW "SERVICE AND NOT FOR PERMIT, THIS DOES NOT
 FALL UNDER THE SAME ENFORCEMENT AS REQUIRED FOR REPEAT
 CODE COMPLAINT COMMENTS 3 OR MORE TIMES AS REQUIRED IN
 FS 553.80(2)(B).
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  