| 2006-11-04 18:36:28 | *** UNSAT 4TH REVIEW*** |
| | |
| | |
| | ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY. |
| | NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE. |
| | PLEASE KNOW A CODE CHANGE FOR NFPA-70 IS COMING AND IF |
| | PERMIT IS NOT APPLIED FOR BEFORE STATE ADOPTS NEW CODE, |
| | THEN THE PLANS WILL BE REQUIRED TO CHANGE AS NEEDED. |
| | THE TENTATIVE DATE IS DEC 1ST, 2006 |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND |
| | ENERGY CALCULATIONS IN AND NEAT AND ORDERLY FASHION. |
| | PLEASE SEE ONLY PARTS OF WHAT SEEMS TO BE A PARTIAL SET |
| | OF REVISED ENERGY CALCULATIONS WERE SUBMITTED. PLEASE |
| | SEE IN EITHER CASE THE PARTIAL ENERGY CALCULATIONS ARE |
| | NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF |
| | RECORD??? THEY ARESIGNED AND DATED10/23/06, BUT NOT |
| | SEALED AND NOT IN ANY ORDER OF ANY KIND?? |
| | PLEASE SUBMIT AS REQUIRED AND REQUESTED. |
| | FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF |
| | WEST PALM BEACH 106.1.2, 106.1.3. , 106.3.5.1 ETC. |
| | |
| | |
| | 2) NOTE: PLEASE SEE OUR SYSTEM STILL INDICATES PLANS |
| | BEING REVIEWED UNDER THE ADDRESS OF 3222 COMMERCE PL, |
| | THE "PLAN REVIEW" SUBMITTAL SHEET WHEN PLANS WERE |
| | SUBMITTED ALSO INDICATE "3222" |
| | PLEASE CORRELATE, AND ONCE AN ADDRESS IS FINALIZED, |
| | PLEASE ADJUST PLANS AS NEEDED OR IF NEEDED. |
| | |
| | 3) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1, .1.2 HAS NOT YET BEEN MET. PLEASE SEE |
| | NEW OC SENSOR TYPE SWITCHES WERE ADDED TO SOME ROOMS |
| | AND SOME AREAS INDICATE A NOTE #7 IN AN OCTAGONAL SHAPE |
| | WHICH MENTIONS TO ADD AN OVER RIDE SWITCH, WITH A MAX |
| | OF 1HR, HOWEVER PLEASE SEE THIS NOTE IS ADDED AT FRONT |
| | DOOR, YET NO "S" IS SHOWN? PLEASE SEE OTHER AREAS WHICH |
| | DO INDICATE AN OC, YET NO TIME LIMITS ARE INDICATED ON |
| | SYMBOL LEGEND? |
| | PLEASE SEE OTHER AREAS WHICH CONTAIN SWITCHES, BUT THEY |
| | WERE NOT CHANGED??? |
| | PLEASE SEE MAX TIMES PERMITTED ON OC SENSOR DEVICES AS |
| | PERVIOUSLY NOTED PER SECTIONS GIVEN. (30MINS MAX ON OC |
| | TYPE AND 4HR MAX ON TIMER TYPE) |
| | PLEASE SEE NOTES #1 , AS ENERGU |
| | CALCULATIONS/PERFORMANCE CALCUALTIONS SUBMITTED DO NOT |
| | PROVIDE THE INFORMATION AS REQUIRED. PLEASE SEE |
| | 13-415.2.ABC.1, TABLE(S) 415.2.C.1 |
| | |
| | 4) NOTE: PLEASE SEE A SIGN CIRCUIT HAS NOW BEEN ADDED, |
| | YET PLEASE SEE 600.5, WHICH REFERENCES THE |
| | 220.3(B)(6). PLEASE SEE THE MINIMUM VA SHALL BE |
| | INDICATED. (SHOWN AS 600VA) |
| | |
| | |
| | ** PLEASE KNOW, AS PLANS HAVE ONLY BEEN SUBMITTED FOR A |
| | "PLAN REVIEW "SERVICE AND NOT FOR PERMIT, THIS DOES NOT |
| | FALL UNDER THE SAME ENFORCEMENT AS REQUIRED FOR REPEAT |
| | CODE COMPLAINT COMMENTS 3 OR MORE TIMES AS REQUIRED IN |
| | FS 553.80(2)(B). |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |