Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-28 00:00:00***** UNSAT3RD REVIEW ******
  
 ** PLANS STILL ONLY SUBMITTED FOR "PLAN
 REVIEW>
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES .
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED AT THE BOTTOM.
  
  
  
 *** NEW NOTE ***
 ** IMPORTANT***
  
 1)A)NOTE; PLEASE KNOW, TO WHOM IT MAY
 CONCERN:. WHEN PLANS ARE SUBMITTED TO
 THE CONSTRUCTION SERVICES DEPARTMENT,
 THE "DATE STAMP" MAY NOT BE BORROWED
 FROM ANY FRONT COUNTER PERSONEL AND USED
 TO STAMP EACH PAGE OF SAID PLANS BEING
 SUBMITTED. THIS DATE STAMP ON EACH SHEET
 IS ONLY DONE WHEN PLANS ARE READY FOR
 ISSUANCE AND THIS IS DONE BY THEPLAN
 REVIEW STAFF ONLY.
  
 1)B) NOTE: PLEASE SEE NONE OF THE
 ARCHITECTURAL SHEETS ARE SIGNED, DATED
 OR SEALED BY THE ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221
 THIS COMMENT IS REQUIRED WHETHER OR NOT
 MADE BY OTHER REVIEWERS.
  
 1)C) NOTE: PLEASE SEE ADDDRESS APPLIED
 FOR"PLAN REVIEW" WAS UNDER "3222" AND
 NOW ARE BEING SHOWN IN TITLE BLOCKS
 UNDER THE ADDRESS OF "3230". PLEASE
 KNOW, THE PAPERWORK HAS BEEN ROUTED TO
 "ADRESSING" AND THE APPLIED FOR "PERMIT"
 OR "PLAN REVIEW" WILL NEED TO CORRELATE
 AND BE CORRECTED.
  
 ** PREVIUOUS REVIEW NOTES BELOW WHICH
 ARE NOT ADDRESSED.
  
  
 1)NOTE: OK.
  
 2)NOTE: OK.
  
  
 3)NOTE: OK.
  
 4)NOTE: OK.
  
 5)NOTE: NO, SAME NOTE, IF ONE IS NOT
 EXISTING , ONE WILL BE REQUIRED. THE
 CODE DOES NOT SAY AN ELECTRICAL SIGN
 MUST BE INSTALLED, HOWEVER ELECTRIC AT A
 J-BOX LOCATED AT THE FRONT ENTRANCE IS
 REQUIRED.
 600.5.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE RESPONSE MENTIONS
 TO VERIFY, HOWEVER THIS IS REQUIRED AT
 THIS TIME TO EITHER SHOW NEW OR EXISTING
 PER 600.5, 1500VA MIN.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE INDICATE EITHER NEW OR
 EXISTING SIGN CIRCUIT PER 600.5
  
 6)NOTE:NO, WHERE IS LARGEST MOTOR
 LOAD BEING SHOWN AT 125%.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE LOADS FOR ALL
 EXISTING AND NEW LOADS SHALL BE SHOWN
 FOR EXISTING AND NEW.
 PLEASE SEE IT WAS NOT STATED WHETHER OR
 LOADS ARE DONE AT 125% FOR CONTINUOUS
 AND LOAD FOR LARGEST MOTOR LOADS.
 PLEASE SEE PREVIOUS NOTE ABOVE WITH
 RESPECT TO THE 4TH TENANT SERVICE WHICH
 DOES NOT SEEM TO BE INCLUDED IN RISER
 AND CALCULATIONS.
 215.3,230.42,220.3,220.10,220.11,220.13
 ,ETC
  
 ** PREVIOUS NOTE REVIEW #1 **
 PLEASE VERIFY ALL LOADS FOR
 EXISTING WIREWAY. PLEASE INDICATE THESE
 LOADS AND THE ADDED NEW LOADS.
 215.5,220
 PLEASE SEE IT APPEARS A CONTINUOUS LOAD
 FACTOR OF 125% IS BEING DONE FOR
 LIGHTING, HOWEVER UNABLE TO VERIFY AS
 THIS IS NOT SHOWN?
 215.3,230.42 ETC.
  
 7)NOTE: OK.
  
 8)NOTE: NO, PLEASE SEE SAME NOTE, NO
 CONTROLS SHOWN OR SUBMITTED. PLEASE SEE
 RESPONSE ONLY MENTIONS, ENERGY
 CALCULATIONS?
 PLEASE ASLSO SEE ONLY ONE COPY OF THE
 ENERGY CALCUALTIONS ARE SIGNED , DATED
 AND SEALED WITH TEH RAISED SEAL AS
 REQUIRED UNDER FS 471.025. ETC
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE COMPLIANCE FOR
 THIS COULD NOT BE LOCATED. PLEASE SEE NO
 LIGHTING CONTROLS, AUTOMATIC SHUTT OFF,
 SCHEDULING ETC WAS SHOWN. PLEASE SEE
 SEPARATE SPACES AND DEVICES REQUIRED FOR
 OVER RIDES. PLEASE LSIT THE DEVICES
 BEING CHOSEN AND THE TIME LIMITS AS SET
 FORTH IN CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS SHALL BE
 SIGNED, DATED AND SEALED. PLEASE SEE EN
 CALCS CONTAIN A "RUBBER STAMP" WHICH IS
 NOT PERMITTED UNDER FS 471.025
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE FBC 2004, CHAPTER 13
 FOR COMMERCIAL BLGS.
 PLEASE SEE 13-413.1.ABC.1.1&.2
 PLEASE SEE 13-415.1.ABC.1.1 &.2&.3
 13-415.1.ABC.3, 13-415.1.AB.1
 SCHEDULING, SPACE LAYOUT, DEVICE
 LOCATIONS ETC WILL BE REQUIRED AT A MIN.
  
 **** NEW NOTES 2ND REVIEW *****
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
  
  
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]