| 2006-09-28 00:00:00 | ***** UNSAT3RD REVIEW ****** |
| | |
| | ** PLANS STILL ONLY SUBMITTED FOR "PLAN |
| | REVIEW> |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES . |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW AND NEW |
| | NOTES ARE ADDED AT THE BOTTOM. |
| | |
| | |
| | |
| | *** NEW NOTE *** |
| | ** IMPORTANT*** |
| | |
| | 1)A)NOTE; PLEASE KNOW, TO WHOM IT MAY |
| | CONCERN:. WHEN PLANS ARE SUBMITTED TO |
| | THE CONSTRUCTION SERVICES DEPARTMENT, |
| | THE "DATE STAMP" MAY NOT BE BORROWED |
| | FROM ANY FRONT COUNTER PERSONEL AND USED |
| | TO STAMP EACH PAGE OF SAID PLANS BEING |
| | SUBMITTED. THIS DATE STAMP ON EACH SHEET |
| | IS ONLY DONE WHEN PLANS ARE READY FOR |
| | ISSUANCE AND THIS IS DONE BY THEPLAN |
| | REVIEW STAFF ONLY. |
| | |
| | 1)B) NOTE: PLEASE SEE NONE OF THE |
| | ARCHITECTURAL SHEETS ARE SIGNED, DATED |
| | OR SEALED BY THE ARCHITECT OF RECORD. |
| | PLEASE SEE FS 481.221 |
| | THIS COMMENT IS REQUIRED WHETHER OR NOT |
| | MADE BY OTHER REVIEWERS. |
| | |
| | 1)C) NOTE: PLEASE SEE ADDDRESS APPLIED |
| | FOR"PLAN REVIEW" WAS UNDER "3222" AND |
| | NOW ARE BEING SHOWN IN TITLE BLOCKS |
| | UNDER THE ADDRESS OF "3230". PLEASE |
| | KNOW, THE PAPERWORK HAS BEEN ROUTED TO |
| | "ADRESSING" AND THE APPLIED FOR "PERMIT" |
| | OR "PLAN REVIEW" WILL NEED TO CORRELATE |
| | AND BE CORRECTED. |
| | |
| | ** PREVIUOUS REVIEW NOTES BELOW WHICH |
| | ARE NOT ADDRESSED. |
| | |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE: OK. |
| | |
| | |
| | 3)NOTE: OK. |
| | |
| | 4)NOTE: OK. |
| | |
| | 5)NOTE: NO, SAME NOTE, IF ONE IS NOT |
| | EXISTING , ONE WILL BE REQUIRED. THE |
| | CODE DOES NOT SAY AN ELECTRICAL SIGN |
| | MUST BE INSTALLED, HOWEVER ELECTRIC AT A |
| | J-BOX LOCATED AT THE FRONT ENTRANCE IS |
| | REQUIRED. |
| | 600.5. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SEE RESPONSE MENTIONS |
| | TO VERIFY, HOWEVER THIS IS REQUIRED AT |
| | THIS TIME TO EITHER SHOW NEW OR EXISTING |
| | PER 600.5, 1500VA MIN. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE INDICATE EITHER NEW OR |
| | EXISTING SIGN CIRCUIT PER 600.5 |
| | |
| | 6)NOTE:NO, WHERE IS LARGEST MOTOR |
| | LOAD BEING SHOWN AT 125%. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SEE LOADS FOR ALL |
| | EXISTING AND NEW LOADS SHALL BE SHOWN |
| | FOR EXISTING AND NEW. |
| | PLEASE SEE IT WAS NOT STATED WHETHER OR |
| | LOADS ARE DONE AT 125% FOR CONTINUOUS |
| | AND LOAD FOR LARGEST MOTOR LOADS. |
| | PLEASE SEE PREVIOUS NOTE ABOVE WITH |
| | RESPECT TO THE 4TH TENANT SERVICE WHICH |
| | DOES NOT SEEM TO BE INCLUDED IN RISER |
| | AND CALCULATIONS. |
| | 215.3,230.42,220.3,220.10,220.11,220.13 |
| | ,ETC |
| | |
| | ** PREVIOUS NOTE REVIEW #1 ** |
| | PLEASE VERIFY ALL LOADS FOR |
| | EXISTING WIREWAY. PLEASE INDICATE THESE |
| | LOADS AND THE ADDED NEW LOADS. |
| | 215.5,220 |
| | PLEASE SEE IT APPEARS A CONTINUOUS LOAD |
| | FACTOR OF 125% IS BEING DONE FOR |
| | LIGHTING, HOWEVER UNABLE TO VERIFY AS |
| | THIS IS NOT SHOWN? |
| | 215.3,230.42 ETC. |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE: NO, PLEASE SEE SAME NOTE, NO |
| | CONTROLS SHOWN OR SUBMITTED. PLEASE SEE |
| | RESPONSE ONLY MENTIONS, ENERGY |
| | CALCULATIONS? |
| | PLEASE ASLSO SEE ONLY ONE COPY OF THE |
| | ENERGY CALCUALTIONS ARE SIGNED , DATED |
| | AND SEALED WITH TEH RAISED SEAL AS |
| | REQUIRED UNDER FS 471.025. ETC |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SEE COMPLIANCE FOR |
| | THIS COULD NOT BE LOCATED. PLEASE SEE NO |
| | LIGHTING CONTROLS, AUTOMATIC SHUTT OFF, |
| | SCHEDULING ETC WAS SHOWN. PLEASE SEE |
| | SEPARATE SPACES AND DEVICES REQUIRED FOR |
| | OVER RIDES. PLEASE LSIT THE DEVICES |
| | BEING CHOSEN AND THE TIME LIMITS AS SET |
| | FORTH IN CHAPTER 13. |
| | PLEASE SEE ENERGY CALCULATIONS SHALL BE |
| | SIGNED, DATED AND SEALED. PLEASE SEE EN |
| | CALCS CONTAIN A "RUBBER STAMP" WHICH IS |
| | NOT PERMITTED UNDER FS 471.025 |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE FBC 2004, CHAPTER 13 |
| | FOR COMMERCIAL BLGS. |
| | PLEASE SEE 13-413.1.ABC.1.1&.2 |
| | PLEASE SEE 13-415.1.ABC.1.1 &.2&.3 |
| | 13-415.1.ABC.3, 13-415.1.AB.1 |
| | SCHEDULING, SPACE LAYOUT, DEVICE |
| | LOCATIONS ETC WILL BE REQUIRED AT A MIN. |
| | |
| | **** NEW NOTES 2ND REVIEW ***** |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | |
| | |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |