Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop P
Sequence Number 2
Notes
Date Text
2006-08-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT T1.1 CODE INDICATED IS FBC-2001,
 CODE ADOPTED IS FBC-2004. PLEASE CHANGE
 REFERENCE TO PROPER CODE.
 ****RESPONSE NOTED, BUT SOME REFERENCES
 TO FBC-2001 STILL ON PLANS.
  
 2. OK
  
 3. SHT A1.2 DETAIL #4 BREAK ELEVATION:
 SINK SHALL BE ACCESSIBLE. SUBMIT
 INFORMATION SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND NO CABINET DOORS ALLOWED IN
 THE CLEAR FLOOR SPACE.
 ****RESPONSE NOTED, BUT DETAIL SHOW
 120'-0" OPENING. PLEASE CLARIFY. - ALSO
 SHOW THE FOLLING INFORMATION:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 7. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM SHOWING ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9. IF INSTALLED ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT FULL OPEN VALVES
 ARE REQUIRED AT THE TOP OF EVERY WATER
 DOWN-FEED PIPE PER SECTION 606.1(4).
 PLEASE SHOW ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]