Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop E
Sequence Number 2
Notes
Date Text
2006-07-07 00:00:00***** UNSAT ******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES .
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED AT THE BOTTOM.
  
 ** PLEASE STILL KNOW, PLANS ARE ONLY
 BEING SUBMITTED FOR "PLAN REVIEW" AND
 ARE BEING SUBMITTED FOR PERMIT.
  
  
  
 1)NOTE: NO, PLEASE SEE AREAS OF PLANS
 WHICH STILL INDICATE THE 2001 FBC.
 PLEASE SEE ARCH WHICH NOW INDICATES THE
 2004 FBC, WHICH SHOULD BE THE 2002
 NFPA-70
 PLEASE SEE THE FOLLOWING CODES ARE
 REQUIRED FOR THIS REVIEWER. OTHERS MAY
 BE REQUIRED FOR OTHER TRADES.
 2004 FBC, 2002 NFPA-70 (NEC), 2002
 NFPA-72, 2003 LS, NFPA-101. AT A MIN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, AS OF OCT 1ST,2005 THE
 STATE OF FLORIDA ADOPTED THE 2004 FBC.
 PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 INDICATE 2001 ETC.
 PLEASE ADJUST.
  
 2)NOTE: NO, PLEASE STILL SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED FOR ENGINEERING COMPANY.
 OTHER ITEMS WERE OK. SEE NE NOTE FOR EN
 CALCS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 ON BOTH TITLE BLOCKS FOR ARCHITECT AND
 ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 FOR ARCHITECT'S, MISSING THE
 PRINTED LICENSE # ON ALL TITLE BLOCKS
 AND SHEETS.
 PLEASE SEE FAC 61G15-23.002 FOR MISSING
 INFORMATION ON ENGINEER'S TITLE BLOCK,
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FLORIDA STATUES 471.023
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT(S) ARE MAADE BY OTHER
 REVIEWER(S).
  
 3)NOTE:OK/NO, PLEASE SEE LETTER WAS
 SUBMITTED HOWEVER IT WAS SHOULD BE
 SEALED WHEN DATED AND NOTORIZED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 471.025 WHICH
 REQUIRES A LEGAL SIGNATURE FROM THE
 ENGINEER. PLANS SEEM TO CONTAIN
 "INITIALS"?, IF INDEED THIS IS THE
 "LEGAL SIGNATURE" OF SAID ENGINEER ,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION OF LEGAL
 SIGNATURE. PLEASE KNOW, LETTER SHOULD BE
 PROPERLY NOTORIZED UNDER THE STATE
 STATUES IN WHICH THE NOTORIZATION IS
 TAKING PLACE. FS 117.05
  
 4)NOTE: NO, PLEASE SEE THE FOLLOWING AS
 THERE ARE STILL DIFFERENCES IN PLANS,
 RISER ETC.
 A) PLEASE SEE RISER SHOWS 250MCM TO
 PANEL "D" AND PANEL "D" SHOWS FEEDERS AS
 3/0'S?
 PLEASE SEE FEEEDERS FOR PANEL "C" ARE
 BEING SHOWN AS THE SAME ON 100A BRKR
 FEED. PLEASE KNOW, THE 100A BRKR WILL NO
 ACCEPT THE 3/0 CONDUCTORS.
 PLEASE SEE RISER IS NOW SHOWING A THIRD
 TENANT BUT STILL DOES NOT SEEM TO BE
 COMPLETE. PLEASE SEE THAT THIS BUILDING
 CONTAIN FOUR TENANTS. SEE COMMENT WITH
 RESPECT TO LOADS.
 PLEASE SEE CIRCUITING FOR AN EM LT IS
 SHOWN TO A CIRCUIT 13, YET THIS SPACE IN
 THE ELECTRICAL PANEL IS A "SPARE"??
 PLEASE SEE PLANS MENTIONS TO "RELOCATE"
 THE EXISTING PANEL "C" , HOWEVER DOES
 NOT SHOW THE NEW LOCATION.
 PLEASE CORRELATE THESE AND PLEASE GO
 OVER PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE ALL EQUIPMENT,
 LOADS, SIZES ETC ON EQUIPMENT SCHEDULE
 AND PANEL SCHEDULE/ LOAD CALCS.
 PLEASE ADJUST PLANS AS NEEDED AS SOME DO
 NOT MATCH.
 215.5
  
 5)NOTE: NO, PLEASE SEE RESPONSE MENTIONS
 TO VERIFY, HOWEVER THIS IS REQUIRED AT
 THIS TIME TO EITHER SHOW NEW OR EXISTING
 PER 600.5, 1500VA MIN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICAET EITHER NEW OR
 EXISTING SIGN CIRCUIT PER 600.5
  
 6)NOTE: NO, PLEASE SEE LOADS FOR ALL
 EXISTING AND NEW LOADS SHALL BE SHOWN
 FOR EXISTING AND NEW.
 PLEASE SEE IT WAS NOT STATED WHETHER OR
 LOADS ARE DONE AT 125% FOR CONTINUOUS
 AND LOAD FOR LARGEST MOTOR LOADS.
 PLEASE SEE PREVIOUS NOTE ABOVE WITH
 RESPECT TO THE 4TH TENANT SERVICE WHICH
 DOES NOT SEEM TO BE INCLUDED IN RISER
 AND CALCULATIONS.
 215.3,230.42,220.3,220.10,220.11,220.13
 ,ETC
  
 ** PREVIOUS NOTE **
 PLEASE VERIFY ALL LOADS FOR
 EXISTING WIREWAY. PLEASE INDICATE THESE
 LOADS AND THE ADDED NEW LOADS.
 215.5,220
 PLEASE SEE IT APPEARS A CONTINUOUS LOAD
 FACTOR OF 125% IS BEING DONE FOR
 LIGHTING, HOWEVER UNABLE TO VERIFY AS
 THIS IS NOT SHOWN?
 215.3,230.42 ETC.
  
 7)NOTE: NO, PLEASE SEE SOME EM LTS NOT
 TO LOCAL LTS. SEE PREVIOUS NOTE ABOVE
 FOR CIRCUIT #13
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
 PLEASE SEE ONE NOTE ON PLANS MENTIONS TO
 SEE PANEL SCHEDULE FOR CIRCUITING , ONE
 NOTE MENTIONS TO CIRCUIT TO LOCAL
 LIGHTING CIRCUIT.
 PLEASE KNOW, 700.12E REQUIRES TE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
 PLEASE ADJUST NOTES ON PLANS, PLEASE
 SHOW AND ADJUST PLANS FOR CIRCUITING.
  
 8)NOTE: NO, PLEASE SEE COMPLIANCE FOR
 THIS COULD NOT BE LOCATED. PLEASE SEE NO
 LIGHTING CONTROLS, AUTOMATIC SHUTT OFF,
 SCHEDULING ETC WAS SHOWN. PLEASE SEE
 SEPARATE SPACES AND DEVICES REQUIRED FOR
 OVER RIDES. PLEASE LSIT THE DEVICES
 BEING CHOSEN AND THE TIME LIMITS AS SET
 FORTH IN CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS SHALL BE
 SIGNED, DATED AND SEALED. PLEASE SEE EN
 CALCS CONTAIN A "RUBBER STAMP" WHICH IS
 NOT PERMITTED UNDER FS 471.025
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004, CHAPTER 13
 FOR COMMERCIAL BLGS.
 PLEASE SEE 13-413.1.ABC.1.1&.2
 PLEASE SEE 13-415.1.ABC.1.1 &.2&.3
 13-415.1.ABC.3, 13-415.1.AB.1
 SCHEDULING, SPACE LAYOUT, DEVICE
 LOCATIONS ETC WILL BE REQUIRED AT A MIN.
  
 **** NEW NOTES *****
  
 9) NOTE: PLEASE CLARIFY IF THERE IS A
 NER OR EXISTING ROOFTOP GFI RECEPT.
 210.63, 210.8
  
 10) NOTE: PLEASE SPECIFY ALL CIRCUITS ON
 SCHEDULE TO THE AREA(S) AND RM IN WHICH
 THEY ARE FEEDING. IE: BATH LTS, OFFICE
 #3 RECEPTS , ETC.
 PLEASE ALSO INCLUDE ALL CONDUCTOR SIZES
 ON PANEL SCHEDULE AND CORRELATE WITH THE
 OCP AS SHOWN.
 240.4,310.16,408.4.
  
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-07-06 00:00:00NOTES TO FOLLOW.