| Date |
Text |
| 2006-07-07 00:00:00 | ***** UNSAT ****** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW AND SOME NEW NOTES . |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW AND NEW |
| | NOTES ARE ADDED AT THE BOTTOM. |
| | |
| | ** PLEASE STILL KNOW, PLANS ARE ONLY |
| | BEING SUBMITTED FOR "PLAN REVIEW" AND |
| | ARE BEING SUBMITTED FOR PERMIT. |
| | |
| | |
| | |
| | 1)NOTE: NO, PLEASE SEE AREAS OF PLANS |
| | WHICH STILL INDICATE THE 2001 FBC. |
| | PLEASE SEE ARCH WHICH NOW INDICATES THE |
| | 2004 FBC, WHICH SHOULD BE THE 2002 |
| | NFPA-70 |
| | PLEASE SEE THE FOLLOWING CODES ARE |
| | REQUIRED FOR THIS REVIEWER. OTHERS MAY |
| | BE REQUIRED FOR OTHER TRADES. |
| | 2004 FBC, 2002 NFPA-70 (NEC), 2002 |
| | NFPA-72, 2003 LS, NFPA-101. AT A MIN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, AS OF OCT 1ST,2005 THE |
| | STATE OF FLORIDA ADOPTED THE 2004 FBC. |
| | PLEASE SEE MANY LOCATIONS ON PLANS WHICH |
| | INDICATE 2001 ETC. |
| | PLEASE ADJUST. |
| | |
| | 2)NOTE: NO, PLEASE STILL SEE MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER |
| | REQUIRED FOR ENGINEERING COMPANY. |
| | OTHER ITEMS WERE OK. SEE NE NOTE FOR EN |
| | CALCS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING INFORMATION |
| | ON BOTH TITLE BLOCKS FOR ARCHITECT AND |
| | ENGINEERING FIRM. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 FOR ARCHITECT'S, MISSING THE |
| | PRINTED LICENSE # ON ALL TITLE BLOCKS |
| | AND SHEETS. |
| | PLEASE SEE FAC 61G15-23.002 FOR MISSING |
| | INFORMATION ON ENGINEER'S TITLE BLOCK, |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | FLORIDA STATUES 471.023 |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT(S) ARE MAADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3)NOTE:OK/NO, PLEASE SEE LETTER WAS |
| | SUBMITTED HOWEVER IT WAS SHOULD BE |
| | SEALED WHEN DATED AND NOTORIZED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FS 471.025 WHICH |
| | REQUIRES A LEGAL SIGNATURE FROM THE |
| | ENGINEER. PLANS SEEM TO CONTAIN |
| | "INITIALS"?, IF INDEED THIS IS THE |
| | "LEGAL SIGNATURE" OF SAID ENGINEER , |
| | PLEASE PROVIDE A SIGNED, DATED AND |
| | SEALED LETTER FOR VERIFICATION OF LEGAL |
| | SIGNATURE. PLEASE KNOW, LETTER SHOULD BE |
| | PROPERLY NOTORIZED UNDER THE STATE |
| | STATUES IN WHICH THE NOTORIZATION IS |
| | TAKING PLACE. FS 117.05 |
| | |
| | 4)NOTE: NO, PLEASE SEE THE FOLLOWING AS |
| | THERE ARE STILL DIFFERENCES IN PLANS, |
| | RISER ETC. |
| | A) PLEASE SEE RISER SHOWS 250MCM TO |
| | PANEL "D" AND PANEL "D" SHOWS FEEDERS AS |
| | 3/0'S? |
| | PLEASE SEE FEEEDERS FOR PANEL "C" ARE |
| | BEING SHOWN AS THE SAME ON 100A BRKR |
| | FEED. PLEASE KNOW, THE 100A BRKR WILL NO |
| | ACCEPT THE 3/0 CONDUCTORS. |
| | PLEASE SEE RISER IS NOW SHOWING A THIRD |
| | TENANT BUT STILL DOES NOT SEEM TO BE |
| | COMPLETE. PLEASE SEE THAT THIS BUILDING |
| | CONTAIN FOUR TENANTS. SEE COMMENT WITH |
| | RESPECT TO LOADS. |
| | PLEASE SEE CIRCUITING FOR AN EM LT IS |
| | SHOWN TO A CIRCUIT 13, YET THIS SPACE IN |
| | THE ELECTRICAL PANEL IS A "SPARE"?? |
| | PLEASE SEE PLANS MENTIONS TO "RELOCATE" |
| | THE EXISTING PANEL "C" , HOWEVER DOES |
| | NOT SHOW THE NEW LOCATION. |
| | PLEASE CORRELATE THESE AND PLEASE GO |
| | OVER PLANS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE CORRELATE ALL EQUIPMENT, |
| | LOADS, SIZES ETC ON EQUIPMENT SCHEDULE |
| | AND PANEL SCHEDULE/ LOAD CALCS. |
| | PLEASE ADJUST PLANS AS NEEDED AS SOME DO |
| | NOT MATCH. |
| | 215.5 |
| | |
| | 5)NOTE: NO, PLEASE SEE RESPONSE MENTIONS |
| | TO VERIFY, HOWEVER THIS IS REQUIRED AT |
| | THIS TIME TO EITHER SHOW NEW OR EXISTING |
| | PER 600.5, 1500VA MIN. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE INDICAET EITHER NEW OR |
| | EXISTING SIGN CIRCUIT PER 600.5 |
| | |
| | 6)NOTE: NO, PLEASE SEE LOADS FOR ALL |
| | EXISTING AND NEW LOADS SHALL BE SHOWN |
| | FOR EXISTING AND NEW. |
| | PLEASE SEE IT WAS NOT STATED WHETHER OR |
| | LOADS ARE DONE AT 125% FOR CONTINUOUS |
| | AND LOAD FOR LARGEST MOTOR LOADS. |
| | PLEASE SEE PREVIOUS NOTE ABOVE WITH |
| | RESPECT TO THE 4TH TENANT SERVICE WHICH |
| | DOES NOT SEEM TO BE INCLUDED IN RISER |
| | AND CALCULATIONS. |
| | 215.3,230.42,220.3,220.10,220.11,220.13 |
| | ,ETC |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE VERIFY ALL LOADS FOR |
| | EXISTING WIREWAY. PLEASE INDICATE THESE |
| | LOADS AND THE ADDED NEW LOADS. |
| | 215.5,220 |
| | PLEASE SEE IT APPEARS A CONTINUOUS LOAD |
| | FACTOR OF 125% IS BEING DONE FOR |
| | LIGHTING, HOWEVER UNABLE TO VERIFY AS |
| | THIS IS NOT SHOWN? |
| | 215.3,230.42 ETC. |
| | |
| | 7)NOTE: NO, PLEASE SEE SOME EM LTS NOT |
| | TO LOCAL LTS. SEE PREVIOUS NOTE ABOVE |
| | FOR CIRCUIT #13 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EM/ |
| | EXT LTS. |
| | PLEASE SEE ONE NOTE ON PLANS MENTIONS TO |
| | SEE PANEL SCHEDULE FOR CIRCUITING , ONE |
| | NOTE MENTIONS TO CIRCUIT TO LOCAL |
| | LIGHTING CIRCUIT. |
| | PLEASE KNOW, 700.12E REQUIRES TE BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | PLEASE ADJUST NOTES ON PLANS, PLEASE |
| | SHOW AND ADJUST PLANS FOR CIRCUITING. |
| | |
| | 8)NOTE: NO, PLEASE SEE COMPLIANCE FOR |
| | THIS COULD NOT BE LOCATED. PLEASE SEE NO |
| | LIGHTING CONTROLS, AUTOMATIC SHUTT OFF, |
| | SCHEDULING ETC WAS SHOWN. PLEASE SEE |
| | SEPARATE SPACES AND DEVICES REQUIRED FOR |
| | OVER RIDES. PLEASE LSIT THE DEVICES |
| | BEING CHOSEN AND THE TIME LIMITS AS SET |
| | FORTH IN CHAPTER 13. |
| | PLEASE SEE ENERGY CALCULATIONS SHALL BE |
| | SIGNED, DATED AND SEALED. PLEASE SEE EN |
| | CALCS CONTAIN A "RUBBER STAMP" WHICH IS |
| | NOT PERMITTED UNDER FS 471.025 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC 2004, CHAPTER 13 |
| | FOR COMMERCIAL BLGS. |
| | PLEASE SEE 13-413.1.ABC.1.1&.2 |
| | PLEASE SEE 13-415.1.ABC.1.1 &.2&.3 |
| | 13-415.1.ABC.3, 13-415.1.AB.1 |
| | SCHEDULING, SPACE LAYOUT, DEVICE |
| | LOCATIONS ETC WILL BE REQUIRED AT A MIN. |
| | |
| | **** NEW NOTES ***** |
| | |
| | 9) NOTE: PLEASE CLARIFY IF THERE IS A |
| | NER OR EXISTING ROOFTOP GFI RECEPT. |
| | 210.63, 210.8 |
| | |
| | 10) NOTE: PLEASE SPECIFY ALL CIRCUITS ON |
| | SCHEDULE TO THE AREA(S) AND RM IN WHICH |
| | THEY ARE FEEDING. IE: BATH LTS, OFFICE |
| | #3 RECEPTS , ETC. |
| | PLEASE ALSO INCLUDE ALL CONDUCTOR SIZES |
| | ON PANEL SCHEDULE AND CORRELATE WITH THE |
| | OCP AS SHOWN. |
| | 240.4,310.16,408.4. |
| | |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-07-06 00:00:00 | NOTES TO FOLLOW. |