Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-17 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT T1.1 CODE INDICATED IS FBC-2001,
 CODE ADOPTED IS FBC-2004. PLEASE CHANGE
 REFERENCE TO PROPER CODE.
 2. SHT A DRINKING FOUNTAIN IS REQUIRED
 PER TABLE 403.1. SHOW LOCATION ON THE
 FLOOR PLAN. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 3. SHT A1.2 DETAIL #4 BREAK ELEVATION:
 SINK SHALL BE ACCESSIBLE. SUBMIT
 INFORMATION SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND NO CABINET DOORS ALLOWED IN
 THE CLEAR FLOOR SPACE.
 4. SHT A1.3 DETAIL #3 SHOW THE
 FOLLOWING:
 A. FOR W/C'S
 11-4.16.3 HEIGHT
 B. FOR LAVS
 11-4.19.2 HEIGHT & CLEARANCES
 11-4.19.4 EXPOSED PIPES AND SURFACES
 11-4.19.5 FAUCETS
 5. SHT A1.3 FIXTURE KEY D TO READ 19"
 "MINIMUM" SECTION 11-4.19.6.
 6. P1.0 PLUMBING SPECIFICATION
 (CONDENSATE DRAINAGE PIPING) 50/50
 SOLDER NOT APPROVED. SECTION 705.9.3.
 SOLDER SHALL COMFORM TO ASTM B32.
 7. SHT P1.0 BUILDING CODE NOTES #15: AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. SECTION 604.9.
 8. SHT P2.0 DWV DRAINAGE RISER DIAGRAM,
 TRAPS SHOWN FOR WATER CLOSETS NOT
 APPROVED. SECTION 1002.1(1).
 7. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM SHOWING ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9. IF INSTALLED ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved