| Plan Review Notes For Permit 06010861 |
| Permit Number |
06010861 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-23 00:00:00 | ******DENIED****** | | | **PLAN REVIEW ONLY** | | | | | | 1) PLEASE NOTE THAT FLORIDA FIRE | | | PREVENTION CODE, 2004 EDITION SHALL BE | | | REFERENCED. SHT T1.1. | | | | | | 2) DUCT SMOKE DETECTOR SHALL BE LOCATED | | | IN SUPPLY AIR SYSTEM, NOT RETURN DUCT. | | | SHT M1.0. | | | | | | 3) 2A-10B,C RATED FIRE EXTINGUISHERS TO | | | BE MOUNTED AND ACCESSIBLE NOT TO EXCEED | | | 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | 4) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|