Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-23 00:00:00******DENIED******
 **PLAN REVIEW ONLY**
  
 1) PLEASE NOTE THAT FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION SHALL BE
 REFERENCED. SHT T1.1.
  
 2) DUCT SMOKE DETECTOR SHALL BE LOCATED
 IN SUPPLY AIR SYSTEM, NOT RETURN DUCT.
 SHT M1.0.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS TO
 BE MOUNTED AND ACCESSIBLE NOT TO EXCEED
 75' TRAVEL DISTANCE REQUIREMENT.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722