Plan Review Notes
Plan Review Notes For Permit 06010861
Permit Number 06010861
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-28 00:00:00************ UNSAT **********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE KNOW, AS OF OCT 1ST,2005
 THE STATE OF FLORIDA ADOPTED THE 2004
 FBC.
 PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 INDICATE 2001 ETC.
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 ON BOTH TITLE BLOCKS FOR ARCHITECT AND
 ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 FOR ARCHITECT'S, MISSING THE
 PRINTED LICENSE # ON ALL TITLE BLOCKS
 AND SHEETS.
 PLEASE SEE FAC 61G15-23.002 FOR MISSING
 INFORMATION ON ENGINEER'S TITLE BLOCK,
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FLORIDA STATUES 471.023
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT(S) ARE MAADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SEE FS 471.025 WHICH
 REQUIRES A LEGAL SIGNATURE FROM THE
 ENGINEER. PLANS SEEM TO CONTAIN
 "INITIALS"?, IF INDEED THIS IS THE
 "LEGAL SIGNATURE" OF SAID ENGINEER ,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION OF LEGAL
 SIGNATURE. PLEASE KNOW, LETTER SHOULD BE
 PROPERLY NOTORIZED UNDER THE STATE
 STATUES IN WHICH THE NOTORIZATION IS
 TAKING PLACE. FS 117.05
  
 4)NOTE: PLEASE CORRELATE ALL EQUIPMENT,
 LOADS, SIZES ETC ON EQUIPMENT SCHEDULE
 AND PANEL SCHEDULE/ LOAD CALCS.
 PLEASE ADJUST PLANS AS NEEDED AS SOME DO
 NOT MATCH.
 215.5
  
 5)NOTE: PLEASE INDICAT EITHER NEW OR
 EXISTING SIGN CIRCUIT PER 600.5
  
 6)NOTE: PLEASE VERIFY ALL LOADS FOR
 EXISTING WIREWAY. PLEASE INDICATE THESE
 LOADS AND THE ADDED NEW LOADS.
 215.5,220
 PLEASE SEE IT APPEARS A CONTINUOUS LOAD
 FACTOR OF 125% IS BEING DONE FOR
 LIGHTING, HOWEVER UNABLE TO VERIFY AS
 THIS IS NOT SHOWN?
 215.3,230.42 ETC.
  
 7)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
 PLEASE SEE ONE NOTE ON PLANS MENTIONS TO
 SEE PANEL SCHEDULE FOR CIRCUITING , ONE
 NOTE MENTIONS TO CIRCUIT TO LOCAL
 LIGHTING CIRCUIT.
 PLEASE KNOW, 700.12E REQUIRES TE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
 PLEASE ADJUST NOTES ON PLANS, PLEASE
 SHOW AND ADJUST PLANS FOR CIRCUITING.
  
 8)NOTE: PLEASE SEE FBC 2004, CHAPTER 13
 FOR COMMERCIAL BLGS.
 PLEASE SEE 13-413.1.ABC.1.1&.2
 PLEASE SEE 13-415.1.ABC.1.1 &.2
 13-415.1.ABC.3, 13-415.1.AB.1
 SCHEDULING, SPACE LAYOUT, DEVICE
 LOCATIONS ETC WILL BE REQUIRED AT A MIN.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICLA
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  