| 2006-02-28 00:00:00 | ************ UNSAT ********** |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT |
| | BEEN SUBMITTED FOR PERMIT. |
| | |
| | |
| | 1)NOTE: PLEASE KNOW, AS OF OCT 1ST,2005 |
| | THE STATE OF FLORIDA ADOPTED THE 2004 |
| | FBC. |
| | PLEASE SEE MANY LOCATIONS ON PLANS WHICH |
| | INDICATE 2001 ETC. |
| | PLEASE ADJUST. |
| | |
| | 2)NOTE: PLEASE SEE MISSING INFORMATION |
| | ON BOTH TITLE BLOCKS FOR ARCHITECT AND |
| | ENGINEERING FIRM. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 FOR ARCHITECT'S, MISSING THE |
| | PRINTED LICENSE # ON ALL TITLE BLOCKS |
| | AND SHEETS. |
| | PLEASE SEE FAC 61G15-23.002 FOR MISSING |
| | INFORMATION ON ENGINEER'S TITLE BLOCK, |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | FLORIDA STATUES 471.023 |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT(S) ARE MAADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE SEE FS 471.025 WHICH |
| | REQUIRES A LEGAL SIGNATURE FROM THE |
| | ENGINEER. PLANS SEEM TO CONTAIN |
| | "INITIALS"?, IF INDEED THIS IS THE |
| | "LEGAL SIGNATURE" OF SAID ENGINEER , |
| | PLEASE PROVIDE A SIGNED, DATED AND |
| | SEALED LETTER FOR VERIFICATION OF LEGAL |
| | SIGNATURE. PLEASE KNOW, LETTER SHOULD BE |
| | PROPERLY NOTORIZED UNDER THE STATE |
| | STATUES IN WHICH THE NOTORIZATION IS |
| | TAKING PLACE. FS 117.05 |
| | |
| | 4)NOTE: PLEASE CORRELATE ALL EQUIPMENT, |
| | LOADS, SIZES ETC ON EQUIPMENT SCHEDULE |
| | AND PANEL SCHEDULE/ LOAD CALCS. |
| | PLEASE ADJUST PLANS AS NEEDED AS SOME DO |
| | NOT MATCH. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE INDICAT EITHER NEW OR |
| | EXISTING SIGN CIRCUIT PER 600.5 |
| | |
| | 6)NOTE: PLEASE VERIFY ALL LOADS FOR |
| | EXISTING WIREWAY. PLEASE INDICATE THESE |
| | LOADS AND THE ADDED NEW LOADS. |
| | 215.5,220 |
| | PLEASE SEE IT APPEARS A CONTINUOUS LOAD |
| | FACTOR OF 125% IS BEING DONE FOR |
| | LIGHTING, HOWEVER UNABLE TO VERIFY AS |
| | THIS IS NOT SHOWN? |
| | 215.3,230.42 ETC. |
| | |
| | 7)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EM/ |
| | EXT LTS. |
| | PLEASE SEE ONE NOTE ON PLANS MENTIONS TO |
| | SEE PANEL SCHEDULE FOR CIRCUITING , ONE |
| | NOTE MENTIONS TO CIRCUIT TO LOCAL |
| | LIGHTING CIRCUIT. |
| | PLEASE KNOW, 700.12E REQUIRES TE BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | PLEASE ADJUST NOTES ON PLANS, PLEASE |
| | SHOW AND ADJUST PLANS FOR CIRCUITING. |
| | |
| | 8)NOTE: PLEASE SEE FBC 2004, CHAPTER 13 |
| | FOR COMMERCIAL BLGS. |
| | PLEASE SEE 13-413.1.ABC.1.1&.2 |
| | PLEASE SEE 13-415.1.ABC.1.1 &.2 |
| | 13-415.1.ABC.3, 13-415.1.AB.1 |
| | SCHEDULING, SPACE LAYOUT, DEVICE |
| | LOCATIONS ETC WILL BE REQUIRED AT A MIN. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICLA |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |