Plan Review Notes
Plan Review Notes For Permit 06010859
Permit Number 06010859
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIION FOR ONE UNIT IS
 120 AMPS AND THE RISER WIRE IS ONLY
 RATED FOR 200 AMPS. SEE 310.15(B)(6).
  
 2} INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT NAME AND SIGN SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  