| Plan Review Notes For Permit 06010859 |
| Permit Number |
06010859 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-26 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE LOAD CALCULATIION FOR ONE UNIT IS | | | 120 AMPS AND THE RISER WIRE IS ONLY | | | RATED FOR 200 AMPS. SEE 310.15(B)(6). | | | | | | 2} INDICATE THE SIZE OF THE GROUNDING | | | ELECTRODE CONDUCTOR PER 250.66. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR | | | THE PLAN MUST PRINT NAME AND SIGN SAME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|