| 2006-03-13 00:00:00 | DENIED: |
| | 1.PLAN INDICATES A BASEMENT LEVEL. |
| | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS |
| | IN ACCORDANCE WITH 2004 FMC 404.1 |
| | THROUGH 404.3. |
| | |
| | 2.PLAN SHEET MP-1 INDICATES AC-1, |
| | PLEASE PROVIDE HANGING DETAIL. |
| | |
| | 3.PLAN SHEET M-1 PLEASE PROVIDE |
| | INFORMATION ON VENTILATION TO THE |
| | STORAGE AREAS. |
| | |
| | 4.PLAN SHEET MP-2 PLEASE CLARIFY THE |
| | RATING OF THE WALL WHERE EF-2 |
| | TERMINATES.PROVIDE DISTANCE TO THE |
| | PROPERTY LINE. SHOW COMPLIANCE WITH 2004 |
| | FMC 401.5, 401.5.2, & 501.2. |
| | |
| | 5.PLEASE CLARIFY THE MECHANICAL CHASE |
| | WITH EXHAUST, FRESH AIR DUCT, & PIPING. |
| | SHOW COMPLIANCE WITH NFPA 90A-02 |
| | 5.3.4.5.PLEASE NOTE, ACCESS FOR |
| | SERVICE & INSPECTION OF THE HORIZONTAL |
| | FIRE DAMPER. |
| | |
| | 6.PLEASE CLARIFY THE RATING OF THE |
| | CEILING/ROOF ASSEMBLY. |
| | |
| | 7.PLEASE PROVIDE DETAIL FOR THE ROOF |
| | JACK, GOOSENECK & THE CONDENSING UNIT |
| | STANDS.STANDS AND CURBS SHALL COMPLY |
| | WITH 2004 FBC 1509.7. |
| | |
| | PLANS APPEAR TO BE FOR A "SHELL |
| | BUILDING" ONLY.ADDITIONAL EQUIPMENT |
| | AND DUCT LAYOUT WILL BE REQUIRED FOR THE |
| | INTERIOR BUILD-OUT. |
| | |