| Date |
Text |
| 2006-02-16 00:00:00 | 1. DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 2. EXIT STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 3. DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. |
| | |
| | 4. WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 5. BUILDING WILL BE REQUIRED TO BE FIRE |
| | SPRINKLERED IN ACCORDANCE WITH 553.895 |
| | (2). |
| | |
| | 6. THE ELECTRICAL DRAWINGS NEED TO BE |
| | EXAMINED. IT DOES NOT APPEAR ENOUGH EXIT |
| | SIGNS OR EMERGENCY LIGHTS EXIST OR ARE |
| | CALLED OUT ON THE DRAWINGS. EXIT SIGNS |
| | SHALL NOT EXCEED 100 FEET APART. ALL |
| | EXITS SHALL BE CLEARLY IDENTIFIED AND |
| | MARKED. |
| | |
| | 7. PLEASE EXPLAIN 6" RISERS FOR |
| | MONUMENTAL STAIR. |
| | |
| | 8. BUILDING ADDRESS REQUIRED ON PROPER |
| | ELEVATION. A MINUMUM OF AT LEAST 6" HIGH |
| | NUMBERS ARE REQUIRED. |
| | |
| | 9. SEPERATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM SYSTEM. THE FIRE ALARM |
| | SYSTEM SHALL BE MONITORED BY A LICENSED |
| | UL LISTED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 10. PLEASE PROVIDE MORE DETAILS ON |
| | EXHAUST FAN 2. WHEN DOES IT RUN AND WHAT |
| | OCCURS WHEN LOSS OF POWER OCCURS TO THE |
| | BUILDING. |
| | |
| | 11. NO EXIT SIGNS SHOWN ON PAGE E-2, |
| | GROUND LEVEL. |
| | |
| | 12. ELECTRONIC SWITCHES, CHAIN AND LOCK |
| | REQUIRED ON FIRE LINE BACKFLOW DEVICE. |
| | |
| | 13. PLEASE PROVIDE A LIFE SAFETY PLAN |
| | ILLUSTRATING EXIT ROUTES, TRAVEL |
| | DISTANCES, ANY DEAD-END CONDITIONS, ETC. |
| | |
| | 14. COULD NOT LOCATE ANY EXISTING OR NEW |
| | FIRE HYDRANTS ON WATER AND SANITARY |
| | SEWER PLANS. |
| | |
| | 15. NO FIRE SPRINKLER DRAWINGS PROVIDED |
| | WITH PLANS. |
| | |
| | 16. THIS OFFICE WILL NOT ACCEPT THE FIRE |
| | ALARM CONTROL PANEL IN THE BASEMENT. |
| | PLEASE REVISE DRAWING. |
| | |
| | 17. DOOR SCHEDULE DOES NOT ILLUSTRATE |
| | REQUIRED FIRE RATINGS. PLEASE REVISE |
| | PLANS. |
| | |
| | 18. A MINIMUM OF AT LEAST A TWO HOUR |
| | HORIZONTAL FIRE SEPERATION IS REQUIRED |
| | BETWEEN THE PARKING AREA AND OTHER |
| | PORTIONS OF THE BUILDING. |
| | |
| | 19. PLEASE DISPLAY FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |
| | 20. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR ALL WALLS AND |
| | CEILINGS. |
| | |
| | MIKE CARSILLO, CHIEF FIRE PREVENTION |
| | OFFICER |
| | 804-4709 |