| Date |
Text |
| 2006-02-27 00:00:00 | *********UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SEE TITLE BLOCK ON PLANS |
| | SHALL INDICATE THE ADDRESS AND LOCATION |
| | OF PROJECT. |
| | FAC 61G15-23.002,61G1-16.003 |
| | |
| | 2)NOTE: PLEASE BE SURE THE FOLLOWING |
| | CODES IN EFFECT ARE REFERENCED: |
| | 2003 NFPA-101, 2002 NFPA-72, 2002 |
| | NFPA-70. |
| | PLEASE SEE SOME CODES ETC ARE REFERENCED |
| | FROM THE 2001 FBC. |
| | |
| | 3)NOTE: PLEASE SEE PERMIT APPLICATION |
| | MENTIONS NEW MEDICAL OFFICE BLDG, |
| | HOWEVER NO INTERIOR PLANS WERE |
| | SUBMITTED. PLEASE SEE NOT EM/ EXT LTS |
| | PER FIRE REVIEW COMMENTS? |
| | |
| | 4)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR |
| | STAIR TOWERS AS NEW STAIRS IN 2003 |
| | LS101, 7.8.1.3 REQUIRES 10FT CANDLES, |
| | UNDER NORMAL POWER AND 1FT CANDLE MIN |
| | UNDER EM. 7.9.2.2 |
| | PLEASE ALSO SEE EM LTS FOR EGRESS PATH |
| | IN PARKING GARAGE COOULD NOT BE LOCATED. |
| | PLEASE ALSO PROVIDE A BATTERY BACK UP LT |
| | FIXTURE OF SOME SORT IN MAIN ELECTRICAL |
| | RM, ELEVATOR MACHINE RM AND LOCATION |
| | WHERE FACP IS BEING MOVED TO PER FIRE |
| | REVIEW COMMENTS. |
| | 7.8,7.9,700.16, 700.12E ETC. |
| | |
| | 5)NOTE: PLEASE SEE FBC 2004 CHAPTER 13, |
| | FOR COMMERCIAL BLDGS. PLEASE SEE |
| | 13-413.1.ABC.1.1 &.2 FOR VOLTAGE DROP |
| | INFORMATIO TO BE PROVIDED. |
| | PLEASE SEE VERIFY COMPLIANCE FOR |
| | INTERIOR OF BLDG IF IN SCOPE OF WORK? |
| | |
| | 6)NOTE: PLEASE SEE COMMENTS FROM OTHER |
| | TRADES FOR POWER FOR FAN POWER IN THE |
| | EVENT OF POWERE FAILURE, GATE CONTROLS |
| | FOR OPERATION OF THESE GATES AFTER POWER |
| | HAS BEEN LOST. |
| | PLEASE SEE ANY POSSIBEL COMMENTS FROM |
| | OTHER TRADES WHICH WILL AFFETC |
| | ELECTRICAL PLANS. |
| | |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IFTHERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |