| Date |
Text |
| 2006-03-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. A DATED |
| | SEAL IS REQUIRED, AND THE ARCHITECTS |
| | TITLE BLOCK SHALL BE UPDATED WITH THE |
| | CORRECT ADDRESS. (SEE ATTACHED SHEET |
| | FROM FLORIDA DBPR). FAC |
| | 61G1-16.004(1)(5) AND FS 481.2055. |
| | 2. SHT A1 SHOWS A FOUNTAIN. THIS IS NOT |
| | INDICATED ON THE APPLICATION "DESCRIBE |
| | PROJECT IN DETAIL". WILL THIS BE ON A |
| | SEPARATE PERMIT WITH SEPARATE PLANS? THE |
| | VALUE OF THE FOUNTAIN SHALL BE WITH THE |
| | SEPARATE PLANS/PERMIT. |
| | 3. SHT A2 FOUNTAIN PUMP. SUBMIT MANUF. |
| | SPECIFICATIONS FOR FOUNTAIN PUMP. PUMP |
| | SHALL BE LISTED. SECTION 303.4 |
| | 4. SHT A2 PER TABLE 403.1 A DRINKING |
| | FOUNTAIN IS REQUIRED. SHOW THE LOCATION |
| | ON THE FLOOR PLAN, AND SHOW PIPING ON |
| | PLUMBING PLANS. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| | SUBSECTIONS, AND IF NOT A HI/LOW SHOW A |
| | DETAIL FOR SECTION 11-4.15..1.3(10)(A) |
| | REQUIREMENTS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. |
| | 5. SHT A2 ENTRY PLAZA INDICATES SLOPE TO |
| | DRAIN. DRAIN NOT SHOWN. PLEASE CLARIFY. |
| | SECTION 106.1.1. INDICATE WHAT AND WHERE |
| | THE DRAIN WILL CONNECT TO. SUBMIT PIPING |
| | PLANS SHOWING ALL PIPE SIZES ETC. |
| | 106.3.5.1.3. |
| | 6. SHT A5 TOILET ROOM ELEVATIONS. SHOW |
| | THE FOLLOWING: |
| | FOR W/C'S: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAVS: |
| | A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | B. 11-4.19.5 FAUCETS |
| | 7. SHT A8 DETAIL "A" SINK SHALL BE |
| | ACCESSIBLE. DETAIL SHALL SHOW COMPLIANCE |
| | WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. FORWARD APPROACH TO SINK |
| | REQUIRED. A 5' TURNING AREA IS REQUIRED |
| | IN SINK AREA. SECTION 11-4.2.3. |
| | 8. ALL PLUMBING, MECHANICAL, & |
| | ELECTRICAL SHEETS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE |
| | NUMBER AS WELL AS, THE NAME, ADDRESS, |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS ON EACH |
| | SHEET. FAC 61G15-23.002(2) & FS 471.025. |
| | 9. SHT P2 SANT. RISER DIAGRAM, 3" IS |
| | REQUIRED UP TO THE WASH MACHINE TEE. |
| | SECTION 406.3. CLEANOUT SHALL BE MINIMUM |
| | 4' ABOVE THE FLOOR FOR ACCESS. SECTION |
| | 708.9. |
| | 10. SHT P2 SANT. RISER DIAGRAM, HAIR |
| | WASH SINKS, (GROUP OF 4), ARE NOT |
| | VENTED. EITHER ISLAND VENTS OR AAV'S ARE |
| | REQUIRED. SECTION 901.2.1. |
| | 11. SHT P2 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS ARE REQUIRED AT THE |
| | WASH MACHINE AND AT THE REF. ICE MAKER. |
| | SECTION 604.9. THESE SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SHOWN. |
| | PDI-WH 201 AND MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | 12. SHT P2 PLUMBING SPECIFICATIONS #13 |
| | INDICATES "K COPPER" FOR UNDERGROUND. |
| | RISERS DIAGRAM SHOWS FITTINGS. NO SOLDER |
| | JOINTS ARE APPROVED UNDER THE SLAB. |
| | PIPING SHOULD BE LOOPED FROM SINK TO |
| | SINK WITH THE MANIFOLD ABOVE THE SLAB. |
| | SECTION 604.10.3. |
| | 13. AN RPZV BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2. |
| | BACKFLOW SHALL BE LOCATED AS CLOSE TO |
| | THE WATER METER AS POSSIBLE ON PRIVATE |
| | PROPERTY. |
| | 14. SHT P2 PLUMBING NOTES #1 INDICATES |
| | 120 GALLON WATER HEATER, BUT SHT A2 |
| | FLOOR PLAN SHOWS AN 80 GALLON WATER |
| | HEATER. PLEASE CORRELATE ARCHITECTURAL |
| | AND PLUMBING SHEETS. SECTION 106.1.1. |
| | 15. MORE INFORMATION IS REQUIRED ON THE |
| | CONDENSATE SYSTEM. INDICATE HOW AHU'S |
| | ARE TO BE DRAINED. SUBMIT A CONDENSATE |
| | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE |
| | SIZES, AND TERMINATION POINT. INDICATE |
| | MATERIAL TYPE. SECTION 106.3.5.1.3. |
| | 16. SEPARATE PLANS REQUIRED FOR |
| | FOUNTAIN. SHOW ALL PIPE SIZES AND ALL |
| | PIPING FROM AND TO THE PUMP. INDICATE IF |
| | THERE IS A DRAIN FOR THE FOUNTAIN AND |
| | WHERE IT DRAINS TO. INDICATE IF THERE IS |
| | A FILTER FOR THE SYSTEM, AND IF THERE IS |
| | A WATER SUPPLY FOR THE FOUNTAIN. IF |
| | THERE IS A WATER SUPPLY, BACKFLOW |
| | PREVENTION IS REQUIRED. INDICATE METHOD |
| | OF BACKFLOW PREVENTION. SECTIONS |
| | 106.1.1. AND 608. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |