| 2006-03-02 00:00:00 | DENIED: |
| | 1.RETURN AIR REQUIRED FROM THE CENTRAL |
| | RETURN BY A DOOR.PLAN SHEET M1THE |
| | KERASTASE ROOM DOES NOT INDICATE A |
| | RETURN.PLEASE SHOW COMPLIANCE WITH |
| | 2004 FMC 601.4. |
| | |
| | 2.PER 2004 FMC TABLE 403.3, PUBLIC |
| | RESTROOMS SHALL HAVE MECHANICAL EXHAUST |
| | WITH AIR MAKE-UP.RE-CIRCULATION OF |
| | THIS AREA IS PROHIBITED. |
| | |
| | 3.CONDENSATE SHALL TERMINATE A MINIMUM |
| | OF 12" AWAY FROM THE BUILDING STRUCTURE, |
| | IN ACCORDANCE WITH 2004 FBC 1503.6. |
| | |
| | 4.WITH REGARDS TO THE EXHAUST FROM THE |
| | MANICURE AREA.PER 2004 FMC 502.1.1 |
| | INLET TO AN EXHAUST SYSTEM SHALL BE |
| | LOCATED IN THE AREA OF HEAVIEST |
| | CONCENTRATION OF CONTAMINANTS. |
| | |
| | 5.PLANS DO NOT INDICATE DUCTWORK OR |
| | TERMINATION FOR THE DRYER EXHAUST. |
| | PLEASE SHOW COMPLIANCE WITH 2004 FMC |
| | 504. |
| | |
| | 6.NO COMBUSTIBLES ALLOWED IN THE AHU |
| | CLOSET WHICH APPEARS TO BE A PLEMUM. |
| | THIS APPLIES TO THE LOUVERED DOOR & |
| | FRAME ALSO.PER 2004 FMC MATERIALS |
| | EXPOSED WIHTIN PLENUMS SHALL HAVE A |
| | FLAME INDEX OF NOT MORE THAN 25 & A |
| | SMOKE DEVELOPED INDEX OF NOT MORE THAN |
| | 50 WHEN TESTED IN ACCORDANCE WITH ASTM |
| | 84.PLEASE VERIFY DOOR ASSEMBLY. |
| | |
| | 7.DUCT SMOKE DETECTORS REQUIRED FOR |
| | ALL OF THE A/C SYSTEMS PER 2004 FMC |
| | 606.2.2.PLEASE PROVIDE NOTIFICATION TO |
| | ALARM/STROBE IN NORMALLY OCCUPIED AREAS |
| | PER 2004 FMC 606.4.1 EXCEPTION #2. |
| | |
| | 8.PLEASE PROVIDE MANUFACTURE SUBMITTAL |
| | DATA FOR THE CONDENSING UNIT STAND |
| | INDICATED ON PLAN SHEET M2.INDICATE |
| | CLEARANCE FROM THE ROOF SURFACE TO THE |
| | BOTTOM OF THE SUPPORT RAIL.SHOW |
| | COMPLIANCE WITH 2004 FBC 1509.7. |
| | |
| | 9.PROVIDE DETAIL FOR THE ATTACHMENT OR |
| | ANCHORING OF THE CONDENSING UNIT STAND |
| | IN ACCORDANCE WITH 2004 FMC 301.13 & FBC |
| | 1603.1.4. |
| | |
| | 10. PLEASE INDICATE ROOF ACCESS FOR THE |
| | SERVICE & MAINTENANCE OF THE ROOFTOP |
| | EQUIPMENT.2004 FMC 306.5. |
| | |
| | 11. PLAN SHEET M4 DETAIL FOR THE AHU. |
| | OVERFLOW PROTECTION IS NOT INDICATED. |
| | SHOW COMPLIANCE WITH 2004 FMC 307.2.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |