| 2006-04-26 00:00:00 | **********UNSAT 2ND REVIEW ********** |
| | |
| | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS |
| | REVIEW, PLEASE SEE NOW TWO DIFFERENT |
| | ELECTRICAL RISERS ARE BEING SUBMITTED |
| | FOR REVIEW. |
| | PLEASE SEE RISERS SUBMITTED DO NOT MEET |
| | MIN NEC CODE COMPLIANCE FOR |
| | INSTALLATIONS. |
| | PLEASE SEE MANY COMMENTS FROM PREVIOUS |
| | REVIEW STILL REMAIN AND NEW COMMENTS AS |
| | INFORMATION ON RISERS ARE NOT COMPLETE |
| | OR DO NOT CORRELATE. |
| | 215.5 |
| | |
| | 2) NOTE: PLEASE SEE PLANS SUBMITTED DO |
| | NOT CONTAIN THE PRINTED NAME AND THE |
| | SIGNATURE OF THE "DESIGN |
| | PROFESSIONAL"/CONTRACTOR WHO IS TAKING |
| | RESPONSIBILITY FOR PLANS AND DESIGN. |
| | FBC 104.2.1 ADMINISTRATIVE SECTION AS |
| | ADMENDED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 3) NOTE: PLEASE SEE RESPONSE LETTER |
| | MENTIONS GEN WILL BE SEPARATELY DERIVED |
| | , HOWEVER PLANS HAVE NOT BEEN REVISED TO |
| | MEET CODE COMPLIANCE FOR THIS AND THE |
| | SPECS FOR THE ATS DO NOT MENTIONS |
| | 4-POLE. |
| | 250.30,215.5 |
| | |
| | 4) NOTE: PLEASE SEE 250.6,250.24B AND |
| | 250.122 FOR MISSING EQUIPMENT GROUNDS. |
| | |
| | 5) NOTE: PLEASE SEE RISER9S) ARE MISSING |
| | CONDUCTORS, OCP ETC. |
| | PLEASE SEE RESPONSE LTR MENTIONS, MAINS |
| | ARE NOT GROUPED??? PLEASE SEE NEC |
| | 230.72,230.70,230.76,230.79, 110.27 |
| | 225.31-225.39 WHERE ALL MAINS AND MEANS |
| | OF DISCONNECTS FOR SEC'S AND FEEDERS ARE |
| | REQUIRED TO BE GROUPED, HAVE A MANUAL |
| | MEANS OF DISCONNECT , RATED FOR THE LAOD |
| | SERVED, ON THE OUTSIDE OF EQUIPMENT, NOT |
| | EXPOSING PERSONS TO LIVE PARTS AND ALL |
| | SHALL BE GROUPED. |
| | 215.5, |
| | |
| | 6) NOTE: PLEASE SEE FLORIDA STATUES |
| | 553.80(2)(B) WITH RESPECT TO THE "DESIGN |
| | PROFESSIONAL" AND REPEAT COMMENTS FOR |
| | CODE COMPLIANCE. |
| | PLEASE KNOW, DUE TO THE EXTREME TIME |
| | SENSATIVE NATURE OF THIS PROJECT IT IS |
| | STRONGLY RECOMMENDED A MEETING BE HELD |
| | WITH CITY'S PROJECT REPRESENTATIVE, AND |
| | PLANS EXAMINER TO GO OVER NOTES AND |
| | COMMENTS IN ORDER TO HELP ALLEAVIATE ANY |
| | FURTHER DELAYS. |
| | |
| | PLEASE CALL TO SET UP A TIME TO GO OVER |
| | PLANS AND FOR NEW PLANS TO BE SUBMITTED |
| | ONCE ALL REVIEWS ARE COMPLETE. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |