Plan Review Notes
Plan Review Notes For Permit 06010743
Permit Number 06010743
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-07 00:00:00DENIED:
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR.
  
 2.PLEASE PROVIDE SITE PLANS INDICATING
 LOCATION OF THE GENERATOR.SHOW
 DISTANCE FROM BUILDING STRUCTURE,
 WINDOWS, DOORS, LOUVERS, ETC.PLEASE
 INDICATE DISTANCE FROM PROPERTY LINES.
  
 3.PERMIT APPLICATION INDICATES NATURAL
 GAS BUT A SUBMITTAL FOR AN LP TANK IS
 ALSO PROVIDED.WILL THIS BE A "DUEL
 TYPE OF FUEL SORCE"?PLEASE CLARIFY.
  
 4.ADDITIONAL PERMIT REQUIRED FOR GAS
 INSTALLATION.
  
 5.PLEASE PROVIDE DETAIL FOR THE
 GENERATOR SLAB & ANCHORING OF THE
 GENERATOR.SHOW COMPLIANCE WITH 2004
 FMC 301.13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.