Plan Review Notes
Plan Review Notes For Permit 06010742
Permit Number 06010742
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-26 00:00:00PLACED CALL AND E-MAIL TO
 JEFF HALVERSON,
 ELECTRICAL PLANS SUBMITTED FOR FIRE
 STATION #5 ARE ON HOLD AS PLANS NEED TO
 BE SUBMITTED FOR ELECTRICAL CODE
 COMPLIANCE.
 THERE ARE NUMEROUS ITEMS WHICH NEED TO
 BE ADDRESSED.
 **********UNSAT 2ND REVIEW **********
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW, PLEASE SEE NOW TWO DIFFERENT
 ELECTRICAL RISERS ARE BEING SUBMITTED
 FOR REVIEW.
 PLEASE SEE RISERS SUBMITTED DO NOT MEET
 MIN NEC CODE COMPLIANCE FOR
 INSTALLATIONS.
 PLEASE SEE MOST COMMENTS FROM PREVIOUS
 REVIEW STILL REMAIN.
 215.5
  
 2) NOTE: PLEASE SEE PLANS SUBMITTED DO
 NOT CONTAIN THE PRINTED NAME AND THE
 SIGNATURE OF THE "DESIGN
 PROFESSIONAL"/CONTRACTOR WHO IS TAKING
 RESPONSIBILITY FOR PLANS AND DESIGN.
 FBC 104.2.1 ADMINISTRATIVE SECTION AS
 ADMENDED BY THE CITY OF WEST PALM BEACH.
  
 3) NOTE: PLEASE SEE RESPONSE LETTER
 MENTIONS GEN WILL BE SEPARATELY DERIVED
 , HOWEVER PLANS HAVE NOT BEEN REVISED TO
 MEET CODE COMPLIANCE FOR THIS AND THE
 SPECS FOR THE ATS DO NOT MENTION BEING
 4-POLE.
 250.30,215.5
  
 4) NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO THE "DESIGN
 PROFESSIONAL" AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 PLEASE KNOW, DUE TO THE EXTREME TIME
 SENSATIVE NATURE OF THIS PROJECT IT IS
 STRONGLY RECOMMENDED A MEETING BE HELD
 WITH CITY'S PROJECT REPRESENTATIVE, AND
 PLANS EXAMINER TO GO OVER NOTES AND
 COMMENTS IN ORDER TO HELP ALLEAVIATE ANY
 FURTHER DELAYS.
  
 PLEASE CALL TO SET UP A TIME TO GO OVER
 PLANS AND FOR NEW PLANS TO BE SUBMITTED
 ONCE ALL REVIEWS ARE COMPLETE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]