| Date |
Text |
| 2006-02-06 00:00:00 | ********* UNSAT *********** |
| | |
| | |
| | 1)NOTE: PLEASE PROVIDE NEUTRAL LOAD |
| | CALCULATIONS FOR DOWN SIZING OF NEUTRAL. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE PROVIDE PLANS TO BE DONE |
| | MINIMUM BY AN ARCHITETC AS REQUIRED |
| | UNDER FS 481.229. PLANS MAY ALSO BE DONE |
| | BY AND PE AS LISTED UNDER FS |
| | 471.003(2)H). |
| | PLEASE SEE THE FOLLOWING COMMENT AS |
| | PLANS MAY BE REQUIRED TO BE DONE BY A PE |
| | AS VALUE MAY BE ADJUSTED. (IF $50K OR |
| | MORE, THEN A PE WILL BE REQUIRED FOR |
| | PLANS. |
| | |
| | 3)NOTE: PLEASE SEE FBC ADMINISTRATIVE |
| | SECTION 108.3 WHICH REQUIRES VALUE BASED |
| | ON COMPLETE SCOPE WORK TO INCLUDE ALL |
| | LABOR AND MATERIALS, EVEN IF EQUIPMENT |
| | IS OWNER SUPPLIED. |
| | PLEASE SEE VALUE IS SHOWN AS THE SAME |
| | FOR ALL THREE PERMITTED JOBS. |
| | |
| | 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| | CUT/SPEC SHEETS FOR THE NEW GENERATOR, |
| | ATS AND FUEL TANK. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE PROVIDE MIN FUEL FOR ALL |
| | LIFE SAFETY DEVICES. |
| | PLEASE ALSO SEE FIRE REVIEW COMMENTS. |
| | LS 101 7.8,7.9 ETC |
| | |
| | 6)NOTE: PLEASE SEE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS BEING SHOWN |
| | BETWEEN THE ATS AND THE MDP? |
| | PLEASE SEE 20.6,250.24 AS "EQUIPMENT |
| | GROUNDING CONDUCTORS" ARE ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 7)NOTE: PLEASE DECLARE WHETHER OR NOT |
| | THE GENERATOR WILL OR WILL NOT BE A |
| | SEPARATEY DERVIED SYSTEM. PLEASE ADJUST |
| | AS NEEDED. |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE 445.13 FOR MIN SIZING |
| | OF CONDUCTORS FROM GENERATOR TO ATS, |
| | FIRST MEANS OF OCP. |
| | 215.5, 240.4,310.16 |
| | |
| | 9)NOTE: PLEASE SEE NO OCP IS SHOWN AT |
| | GENERATOR.? |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SUBMIT PLANS INDICATION |
| | LOCATION OF GENERATOR AT SITE. |
| | PLEASW SHOW DETAIL OF WHERE BOLLARDS MAY |
| | BE REQUIRED DEPENDING ON THE LOCATION OF |
| | GENERATOR ETC. |
| | |
| | 11)NOTE: PLEASE SEE BLDG REVIEW ,AS NO |
| | SLAB/FOOTER DETAILS WERE SUBMITTED. |
| | |
| | 12)NOTE: PLEASE SEE , RISER AS SHOWN MAY |
| | REQUIRE A MAIN DISC ON THE LINE SIDE OF |
| | ATS. |
| | |
| | |
| | 13)NOTE: PLEASE SEE NO OCP IS INDICATED |
| | FOR NEW FEED TO PANEL EM? |
| | CAN NOT VERIFY FEEDERS ETC AT THIS TIME. |
| | 215.5,310.16 |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS,PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS OFFICE. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | PLANS SENT TO LUIS M. |