Plan Review Notes
Plan Review Notes For Permit 06010742
Permit Number 06010742
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-06 00:00:00********* UNSAT ***********
  
  
 1)NOTE: PLEASE PROVIDE NEUTRAL LOAD
 CALCULATIONS FOR DOWN SIZING OF NEUTRAL.
 215.5
  
 2)NOTE: PLEASE PROVIDE PLANS TO BE DONE
 MINIMUM BY AN ARCHITETC AS REQUIRED
 UNDER FS 481.229. PLANS MAY ALSO BE DONE
 BY AND PE AS LISTED UNDER FS
 471.003(2)H).
 PLEASE SEE THE FOLLOWING COMMENT AS
 PLANS MAY BE REQUIRED TO BE DONE BY A PE
 AS VALUE MAY BE ADJUSTED. (IF $50K OR
 MORE, THEN A PE WILL BE REQUIRED FOR
 PLANS.
  
 3)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH REQUIRES VALUE BASED
 ON COMPLETE SCOPE WORK TO INCLUDE ALL
 LABOR AND MATERIALS, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED.
 PLEASE SEE VALUE IS SHOWN AS THE SAME
 FOR ALL THREE PERMITTED JOBS.
  
 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR THE NEW GENERATOR,
 ATS AND FUEL TANK.
 215.5
  
 5)NOTE: PLEASE PROVIDE MIN FUEL FOR ALL
 LIFE SAFETY DEVICES.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS.
 LS 101 7.8,7.9 ETC
  
 6)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN
 BETWEEN THE ATS AND THE MDP?
 PLEASE SEE 20.6,250.24 AS "EQUIPMENT
 GROUNDING CONDUCTORS" ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 7)NOTE: PLEASE DECLARE WHETHER OR NOT
 THE GENERATOR WILL OR WILL NOT BE A
 SEPARATEY DERVIED SYSTEM. PLEASE ADJUST
 AS NEEDED.
 215.5
  
 8)NOTE: PLEASE SEE 445.13 FOR MIN SIZING
 OF CONDUCTORS FROM GENERATOR TO ATS,
 FIRST MEANS OF OCP.
 215.5, 240.4,310.16
  
 9)NOTE: PLEASE SEE NO OCP IS SHOWN AT
 GENERATOR.?
 215.5
  
 10)NOTE: PLEASE SUBMIT PLANS INDICATION
 LOCATION OF GENERATOR AT SITE.
 PLEASW SHOW DETAIL OF WHERE BOLLARDS MAY
 BE REQUIRED DEPENDING ON THE LOCATION OF
 GENERATOR ETC.
  
 11)NOTE: PLEASE SEE BLDG REVIEW ,AS NO
 SLAB/FOOTER DETAILS WERE SUBMITTED.
  
 12)NOTE: PLEASE SEE , RISER AS SHOWN MAY
 REQUIRE A MAIN DISC ON THE LINE SIDE OF
 ATS.
  
  
 13)NOTE: PLEASE SEE NO OCP IS INDICATED
 FOR NEW FEED TO PANEL EM?
 CAN NOT VERIFY FEEDERS ETC AT THIS TIME.
 215.5,310.16
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY
 QUESTIONS,PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
 PLANS SENT TO LUIS M.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved