Plan Review Notes
Plan Review Notes For Permit 06010678
Permit Number 06010678
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06010678
 ADD: 605 N. OLIVE AVE
 CONT: J A TAYLOR ROOFING
 TEL: (772)466-4040
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE THE FL COVERSHEET AND BACK UP
 REPORT FOR THE RAINPROOF 40 PEEL &
 STICK.
 RAINPROOF 40 HAS NOT APPLIED FOR STATE
 APPROVAL, MAKE APPLICATION FOR LOCAL
 PRODUCT APPROVAL WITH THE MIAMI-DADE NOA
 AND WPB COVERSHEET.
  
 2) WHEN APPLYING FOR A LOCAL PRODUCT
 APPROVAL USE THE JURISDICTION'S LOCAL
 PRODUCT APPROVAL SHEET, IT IS THE SAME
 10 REQUIRED ITEMS AS THE STATE BUT ALL
 10 ITEMS ARE TO BE FILLED IN AND
 CORRECT! A COPY OF WPB LOCAL APPROVAL IS
 ATTACHED, SEE INSTRUCTIONS ON BACK OF
 SHEET.
  
  
 THE SAME COMMENT APPLY FOR LOCAL PRODUCT
 APPROVAL FOR THE METAL ROOF SYSTEM
 ENGLERT SERIES 2000, STEEL 24 GAUGE.
  
 IF USING THE 26 GAUGE ENGINEER TO
 PROVIDE THERE RATIONAL ANYLSIS
 (COMPUTATIONS)FOR REVIEW.
  
 2-(1)STEP (1) LEFT UNCIRCLED METHOD ONE
 SHOULD HAVE BEEN CIRCLED, SINCE THE
 ENGINEER IS DOING A RATIONAL ANALYSIS
 FROM A FLORIDA APPROVED SYSTEM
 FL# 5574 (2204). PRINTED METHOD (1-D)
  
 2-(2) THE COMPANY APPLYING FOR THE LOCAL
 PRODUCT APPROVAL IS ENGLERT, INC. NOT
 THE ROOFING CONTRACTOR.
  
 2-(3) THE MAILING ADDRESS IS FOR THE
 MANUFACTURINGCOMPANY LISTED ABOVE WHO
 IS APPLYING FOR LOCAL APPROVAL:
 ENGLERT, INC.
 1200 AMBOY AVE.
 PERTH AMBOY, N J 08861
  
 2-(4) ENGLERT, INC. T (732)826-8614
 F (732)826-8865
  
 2-(5) E-MAIL ADDRESS:
 [email protected]
  
 2-(6) APPLICANTS TECHNICAL
 REPRESENTATIVE:
 WEYANT ENGINEERING, INC
 DWIGHT R WEYANT, P E # 20,273
 201 SW PORT ST LUCIE BLVD SUITE 104
 PORT ST LUCIE, FL 34984
 TEL: (772) 335-0772
 FAX: (772) 335-0866
  
 FIRM REGISTRATION# 3969
  
 2-(7) THIRD PARTY QUALITY ASSURANCE
 ENTITY: A NOTIRIZED LETTER FORM
 THIS ENTITY STATING THAT THEY ARE ALSO
 PREFORMING QUALITY ASSURANCE ON THE 26
 GAUGE, METAL SYSTEM.
 FL# 5574 UNDERWRITERS LABORATORIES INC
 333 PFINGSTEN RD
 NORTHBROOK, ILL
 TEL(847)272-8800
 CONTACT: RICK TITUS
 [email protected]
  
 2-(8) METHOD 1-D RATIONAL ANALYSIS,
 CHECK THE APPOPRIATE BOXES ON FORM
 THE REPORT SUBMITTED BY WEYANT
 ENGINEERING SHOULD BE ATTACHED AND
  
 THE LIMITATIONS OF THE PRODUCT.
  
 2-(9) SEE ATTACHED SHEETS
  
 2-(10) NAME & TITLE OF PERSON AUTHORIZED
  
 TO SIGN ON BEHALF OF APPLICANT:
 JOE F. TRIPOD FROM ENGERT OR
 LOCAL REPRESENTATIVE SIGNATURE
 WITH ADDRESS AND TEL NUMBER.
  
 3) THE RATIONAL ANYLSIS FROM WEYANT
 ENGINEERING LIMITS THE INSTALLATION TO
 -62.5PSF WHERE AS THE DESIGN
 PROFESSIONAL FOR THE PROJECT PAUL
 BARBIERI, PE LIST THE PRESSURES LOCATED
 IN ZONE 2 & 3 OF -81.5 REQUIRING
 ENHANCED FASTENING TO MEET THESE GREATER
 PRESSURES.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  