Plan Review Notes
Plan Review Notes For Permit 06010642
Permit Number 06010642
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-26 00:00:00***** UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE SOME NOTES FROM FIRST
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH COMMENTS BELOW.
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
  
 1)NOTE:NO, PLEASE SEE SOME ITEMS ON
 ELECTRICAL PANELS SUBMITTED ARE NOT
 COMPLETE. PLEASE SEE NO WIRE/CONDUCTOR
 SIZES WERE SUBMITTEDTO CORRELATE WITH
 THE OCP SHOWN ON PANEL SCHEDULE(S).
 PLEASE SEE THAT NO VERIFICATION FOR
 240.4,310.16 CAN BE DONE AT THIS TIME.
  
 PLEASE SEE SCOPE MENTIONES TO THE 2005
 NEC, PLEASE KNOW, THE STATE OF FLORIDA
 IS CUURENTLY UNDER THE 2002 NFPA-70
 (NEC).
 PLEASE SHOW ANY POSSIBLE CLASS LOCATIONS
 AND WHAT CLASS/DIVISION WIRING METHODS
 ARE TO BE USED. PLEASE SPECOFY OF NO
 CLASS LOCATION EXIST, AS PLANS ARE NOT
 COMPLETELY CLEAR FOR THE PROCESSING
 TAKING PLACE IN THIS BUIDLING/ FACILITY.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE PLANS SUBMITTED
 WITH DISCRIPTION OF WORK. PLEASE PROVIDE
 SCOPE OF WORK ON PLANS SUBMITTED FOR
 WORK BEING PRPOSED ETC.
 PLEASE SEE NUMEROUS SHEETS WERE
 SUBMITTED, HOWEVER NO DETAILS FOR WHAT
 IS TAKING PLACE.
 PLEASE SEE NO PANEL SCHEDULES, CIRCUITS,
 LOADS ETC.
 PLEASE BE SURE PLANS SPECIFY ANY CLASS
 LOCATIONS FOR ELECTRICAL WORK.
 215.5
  
 2)NOTE: NO, PLEASE KNOW, THIS COMPLETE
 INFORMATION IS REQUIRED FOR ALL TRADE S
 AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE SEE ALL SHEETS INCLUDING
 STRUCTURAL ARE MISSING ALL THE
 INFORMATION AS SET-FORTH IN THE FLORIDA
 ADMINISTRATIVE CODE AND ALSO REQUIRED
 UNDER FLORIDA STATUES.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MISSING TITLE BLOCK
 INFORMATION FOR ALL ELECTRICAL AND BLDG
 SHEETS SUBMITTED. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002, FS
 471.023
  
 3)NOTE: OK, HOWEVER SEE PREVIOUS NOTE.
  
 4)NOTE: OK, SEAL REVISED.
  
 NEW NOTE;
  
 5) NOTE: PLEASE SEE PLANS NOW MENTION TO
 REPLACE EM/ EXT LTS AND OTHER FIXTURES,
 HOWEVER ITEMS COULD NOT BE LOCATED OR
 WHERE NOT CLEAR ENOUGH ON DETAILS BY
 SOME IDENTIFICATION MEANS FOR REVIEW.
 PLEASE SEE A FIXTURE SCHEDULE INDICATING
 TYOE OF FIXTURE BEING INSTALLED AND
 LOCATIONS.
 PLEASE ALSO INDICATE CIRCUITING PER
 700.12E.
  
  
 ** PLEASE KNOW, CODES SHALL NOT BE
 QUOTED IN LEIU OF DETAILS TO DESIGN ON
 PLANS.
 FBC 104.2.1 LOCAL ADMINISTRATIVE SECTION
 AS ADOPTED BY THE CITY OF WEST PALM
 BEACH.
  
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]