2007-05-07 08:27:31REVISION TO MECHANICAL PLANS PAGES M-1 & M-2.
 *** PROVISO ***
 1) DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS
 SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26
 GAGE SHEET STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE. PER 2004 FBC/R 309.1.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.