| 2006-01-31 00:00:00 | *** DENIED *** | | | 1) NEED TO SUPPLY COMBUSTION AIR OR | | | CALCULATION FOR GAS CLOTHES DRYER, AND | | | GAS WATER HEATER, PER 2004 FBC/R M1701.1 | | | . | | | | | | 2) DEYER VENT TERMINATION NEEDS TO BE 4 | | | FT. MIN. FROM A/C CONDENSER UNITS, PER | | | 2004 FBC/R 501.2 . | | | | | | 3) CENTRAL VAC. UNIT CAN NOT BE IN SAME | | | CLOSET WITH GAS WATER HEATER, OR PROVIDE | | | APPROVED LISTING, PER 2004 FBC/FG 303.2 | | | . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|