Plan Review Notes
Plan Review Notes For Permit 06010605
Permit Number 06010605
Review Stop M
Sequence Number 1
Notes
Date Text
2006-01-31 00:00:00*** DENIED ***
 1) NEED TO SUPPLY COMBUSTION AIR OR
 CALCULATION FOR GAS CLOTHES DRYER, AND
 GAS WATER HEATER, PER 2004 FBC/R M1701.1
 .
  
 2) DEYER VENT TERMINATION NEEDS TO BE 4
 FT. MIN. FROM A/C CONDENSER UNITS, PER
 2004 FBC/R 501.2 .
  
 3) CENTRAL VAC. UNIT CAN NOT BE IN SAME
 CLOSET WITH GAS WATER HEATER, OR PROVIDE
 APPROVED LISTING, PER 2004 FBC/FG 303.2
 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  