 PROVISO
 ~~~~~~~
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO CALLING FOR A ROUGH
 INSPECTION.
  
 1} THE GROUNDING ELECTRODE MUST BE SIZED
 TO TABLE 250.66. 1/0 FOR 400 MCM.
  
 2} 3-2/0 FPL FEED IS INCORRECT. (RISER)
  
 3} NOTE # 20 SHOULD REFERENCE THE 2002
 NEC, AND ALSO 210.12 IS APPLICABLE. THE
 NFPA-72 CODE REFERENCED BY THE FBC IS
 2002.
  
 4} ADD A RECEPTACLE PER 210.52(A)(1) IN
 THE DINING ROOM.
  
 5} ADD RECEPTACLES IN BEDROOMS 2 & 3 PER
 210.52(A)(2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  