| Notes |
| Date |
Text |
| 2006-01-25 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW PRIOR TO CALLING FOR A ROUGH | | | INSPECTION. | | | | | | 1} THE GROUNDING ELECTRODE MUST BE SIZED | | | TO TABLE 250.66. 1/0 FOR 400 MCM. | | | | | | 2} 3-2/0 FPL FEED IS INCORRECT. (RISER) | | | | | | 3} NOTE # 20 SHOULD REFERENCE THE 2002 | | | NEC, AND ALSO 210.12 IS APPLICABLE. THE | | | NFPA-72 CODE REFERENCED BY THE FBC IS | | | 2002. | | | | | | 4} ADD A RECEPTACLE PER 210.52(A)(1) IN | | | THE DINING ROOM. | | | | | | 5} ADD RECEPTACLES IN BEDROOMS 2 & 3 PER | | | 210.52(A)(2). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|