| Plan Review Notes For Permit 06010581 |
| Permit Number |
06010581 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-22 17:14:58 | ******* UNSAT ********** | | | | | | 1) NOTE: PLEASE CORRELATE RISER AND PANEL(S) SCHEDULE | | | SUBMITTED. PLEASE SEE PANEL "A" IS SHOWN FEEDING PANEL | | | "C", YET PANEL "C" IS SHOWN FROM PANEL ""B" ON | | | SCHEDULE.?? | | | | | | 2) NOTE: PLEASE SEE LOAD CALCULATIONS FOR BOTH PANELS | | | FOR A/C LOADS DO NOT CORRELATE. PLEASE ADJUST AND | | | REVISE. PLEASE CORRELATE. | | | 220.31 | | | | | | PLEASE SUBMIT TEH ABOVE INFORMATION FOR REVIEW. | | | IF THERE ARE NAY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER. | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|