Plan Review Notes
Plan Review Notes For Permit 06010581
Permit Number 06010581
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-22 17:14:58******* UNSAT **********
  
 1) NOTE: PLEASE CORRELATE RISER AND PANEL(S) SCHEDULE
 SUBMITTED. PLEASE SEE PANEL "A" IS SHOWN FEEDING PANEL
 "C", YET PANEL "C" IS SHOWN FROM PANEL ""B" ON
 SCHEDULE.??
  
 2) NOTE: PLEASE SEE LOAD CALCULATIONS FOR BOTH PANELS
 FOR A/C LOADS DO NOT CORRELATE. PLEASE ADJUST AND
 REVISE. PLEASE CORRELATE.
 220.31
  
 PLEASE SUBMIT TEH ABOVE INFORMATION FOR REVIEW.
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  