2006-03-18 00:00:00************ PROVISO ***************
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL AND
 MACHANICAL PLANS AND INSTALLATION.
 PLEASE SEE MECH PLANS INDICATE 5KW FOR
 AHU#1 AND 10KW FOR AHU#2, YET ELECTRICAL
 PLANS INDICATE 7.5 KW FOR EACH OF THESE.
 PLEASE KNOW, EVEN IF UNITS ARE 7.5 KW,
 THE 60A OCP IS TOO HIGH.
 PLEASE KNOW, THESE HAVE CHANGED SINCE
 PREVIOUS REVIEW.
 PLEASE VERIFY AND CORRELATE OCP, AWG AND
 KW RATINGS AND REVISE.
  
 **************************************
 PLEASE SUBMIT THE ABOVE ALONG WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELETRICAL
 INSPECTION.
 PLEASE KNOW, IF PLANS COME BACK FOR ANY
 OTHER COMMENTS, PLEASE REVISE AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 REDLINED 210.70 FOR FOYER LT.