| Plan Review Notes For Permit 06010581 |
| Permit Number |
06010581 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-18 00:00:00 | ************ PROVISO *************** | | | | | | 1)NOTE: PLEASE CORRELATE ELECTRICAL AND | | | MACHANICAL PLANS AND INSTALLATION. | | | PLEASE SEE MECH PLANS INDICATE 5KW FOR | | | AHU#1 AND 10KW FOR AHU#2, YET ELECTRICAL | | | PLANS INDICATE 7.5 KW FOR EACH OF THESE. | | | PLEASE KNOW, EVEN IF UNITS ARE 7.5 KW, | | | THE 60A OCP IS TOO HIGH. | | | PLEASE KNOW, THESE HAVE CHANGED SINCE | | | PREVIOUS REVIEW. | | | PLEASE VERIFY AND CORRELATE OCP, AWG AND | | | KW RATINGS AND REVISE. | | | | | | ************************************** | | | PLEASE SUBMIT THE ABOVE ALONG WITH ANY | | | OTHER REVISIONS BEFORE ROUGH ELETRICAL | | | INSPECTION. | | | PLEASE KNOW, IF PLANS COME BACK FOR ANY | | | OTHER COMMENTS, PLEASE REVISE AT THIS | | | TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | REDLINED 210.70 FOR FOYER LT. |
|