Plan Review Notes
Plan Review Notes For Permit 06010581
Permit Number 06010581
Review Stop E
Sequence Number 1
Notes
Date Text
2006-01-24 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 FOR POOL PANEL WITH POOL PANEL SCHEDULE.
 PLEASE SEE RISER INDICATES 100A OCP, AND
 FEEDERS FOR 100A ALSO, HOWEVER PLEASE
 SEE PANEL "B" SHOWS FEED AT 60A'S, AND
 POOL PANEL IS SHOWN AS 60A'S?
 215.5
  
 2)NOTE: PLEASE SEE POOL PANEL SHOWS A
 "GAS" POOL HEATER, AND SHOWS A 4KW
 LOAD AND SHOWN AT 125% WHICH IS SHOWN TO
 5KW? IF THIS A "GAS " POOL HEATER THEN
 LOADS WOULD NOT BE AS SHOWN.
 PLEASE KNOW, ONLY ELECTRICAL TYPE POOL
 HEATERS (HEAT PUMPS) ARE REQUIRED TO
 HAVE OCPAND LOADS FIGURED AT125%. IF
 THIS IS GAS THEN THE LOADSSHOULD BE
 ADJUSTED. THIS WOULD ALSO AFFECT HOW
 LARGE THE POOL PANEL WOULD NEED TO BE.
 PLEASE SEE NOTE #1
 215.5
  
 3)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PLEASE SEE 2002 NEC 210.12
 WHICH REQUIRES ARC FAULT PROTECTION FOR
 ALL "OUTLETS" IN BEDRMS. LTS, SD'S,
 RECEPTS, FANS ETC.
  
 4)NOTE: PLEASE SEE RISER INDICATES
 OUTDOOR MCB PANELS , HOWEVER NO PANEL
 SCHEDULES FOR THESE WERE SUBMITTED.??
 PLEASE SUBMIT.
  
 5)NOTE: PLEASE SEE RISER DIAGRAM WHICH
 SHOWS POOL PANEL BEING FED FROM THE NEW
 OUTDOOR MCB PANELS, HOWEVER PLEASE SEE
 PANEL "B" FOR INDOOR GARAGE PANEL WHICH
 SHOWS POOL PANEL BEING FED FROM THIS
 LOCATION??PLEASE CORRELATE.
  
 6)NOTE: PLEASE SEE PLANS ONLY INDICATE
 ONE DISCONECT LCOATED OUTSIDE NEXT TO
 METER, WHEREAS RISER SHOWS TWO PANELS.
 PLEASE ADJUST AND CORRELATE.
  
 7)NOTE: PLEASE VERIFY THE ATTACHMENT
 LOCATION OF THE GROUNDING ELECTRODE
 CONDUCTOR. THIS IS SHOWN COMING FROM THE
 ONE MAIN BRKR PANEL. PLEASE CLARIFY HOW
 THIS IS CONNECTED FOR THE GROUNDING
 ELECTRODE SYSTEM AS THERE ARE TWO MCB
 PANELS? PLEASE SEE 250.24,250.6 ETC.
 PLEASE SEE METER IS THE TYPICAL
 ATTACHMENT POINT.
  
 8)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL IN KITCHEN.210.52
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO SETS
 FOR REVIEW AND STAMPING. ONE COPY OF OLD
 SHEETS SHOULD BE SUBMITTED FOR REFERENCE
 ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW .IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]