| 2006-01-24 00:00:00 | ********* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | FOR POOL PANEL WITH POOL PANEL SCHEDULE. |
| | PLEASE SEE RISER INDICATES 100A OCP, AND |
| | FEEDERS FOR 100A ALSO, HOWEVER PLEASE |
| | SEE PANEL "B" SHOWS FEED AT 60A'S, AND |
| | POOL PANEL IS SHOWN AS 60A'S? |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE POOL PANEL SHOWS A |
| | "GAS" POOL HEATER, AND SHOWS A 4KW |
| | LOAD AND SHOWN AT 125% WHICH IS SHOWN TO |
| | 5KW? IF THIS A "GAS " POOL HEATER THEN |
| | LOADS WOULD NOT BE AS SHOWN. |
| | PLEASE KNOW, ONLY ELECTRICAL TYPE POOL |
| | HEATERS (HEAT PUMPS) ARE REQUIRED TO |
| | HAVE OCPAND LOADS FIGURED AT125%. IF |
| | THIS IS GAS THEN THE LOADSSHOULD BE |
| | ADJUSTED. THIS WOULD ALSO AFFECT HOW |
| | LARGE THE POOL PANEL WOULD NEED TO BE. |
| | PLEASE SEE NOTE #1 |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE. PLEASE SEE 2002 NEC 210.12 |
| | WHICH REQUIRES ARC FAULT PROTECTION FOR |
| | ALL "OUTLETS" IN BEDRMS. LTS, SD'S, |
| | RECEPTS, FANS ETC. |
| | |
| | 4)NOTE: PLEASE SEE RISER INDICATES |
| | OUTDOOR MCB PANELS , HOWEVER NO PANEL |
| | SCHEDULES FOR THESE WERE SUBMITTED.?? |
| | PLEASE SUBMIT. |
| | |
| | 5)NOTE: PLEASE SEE RISER DIAGRAM WHICH |
| | SHOWS POOL PANEL BEING FED FROM THE NEW |
| | OUTDOOR MCB PANELS, HOWEVER PLEASE SEE |
| | PANEL "B" FOR INDOOR GARAGE PANEL WHICH |
| | SHOWS POOL PANEL BEING FED FROM THIS |
| | LOCATION??PLEASE CORRELATE. |
| | |
| | 6)NOTE: PLEASE SEE PLANS ONLY INDICATE |
| | ONE DISCONECT LCOATED OUTSIDE NEXT TO |
| | METER, WHEREAS RISER SHOWS TWO PANELS. |
| | PLEASE ADJUST AND CORRELATE. |
| | |
| | 7)NOTE: PLEASE VERIFY THE ATTACHMENT |
| | LOCATION OF THE GROUNDING ELECTRODE |
| | CONDUCTOR. THIS IS SHOWN COMING FROM THE |
| | ONE MAIN BRKR PANEL. PLEASE CLARIFY HOW |
| | THIS IS CONNECTED FOR THE GROUNDING |
| | ELECTRODE SYSTEM AS THERE ARE TWO MCB |
| | PANELS? PLEASE SEE 250.24,250.6 ETC. |
| | PLEASE SEE METER IS THE TYPICAL |
| | ATTACHMENT POINT. |
| | |
| | 8)NOTE: PLEASE SEE MISSING RECEPT FOR 2' |
| | OF WALL IN KITCHEN.210.52 |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO SETS |
| | FOR REVIEW AND STAMPING. ONE COPY OF OLD |
| | SHEETS SHOULD BE SUBMITTED FOR REFERENCE |
| | ONLY. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW .IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |