| Plan Review Notes For Permit 06010576 |
| Permit Number |
06010576 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-30 00:00:00 | DENIED: | | | | | | 1.PLAN SHEETS M1, M3, M4 INDICATES 3 | | | DUCT RISERS WITH FIRE DAMPERS LOCATED AT | | | EACH FLOOR LEVEL (1-3).PER 2004 FMC | | | 607.6.1, WHEN A DUCT SYSTEM PENETRATES | | | NOT MORE THAN TWO STORIES, PENETRATION | | | MAY BE PROTECTED BY FIRE DAMPERS AT EACH | | | FLOOR LEVEL.PLANS INDICATE DUCT | | | PENETRATING THREE FLOORS THEREFORE DOES | | | NOT MEET THE REQUIREMENT.PLEASE | | | PROVIDE A SHAFT FOR THE THREE SETS OF | | | DUCT RISERS. | | | | | | 2.PLAN SHEET M7 THE RISER DIAGRAM DOES | | | NOT CORRELATE WITH THE PLAN SHEETS M1, | | | M3, & M4.THE RISER DIAGRAM ONLY | | | INDICATES 2 FLOORS AND NOT 3. | | | | | | 3.PLANS DO NOT HAVE THE PROPER ADDRESS | | | OF THE PORJECT WHICH IS 1920 WEKIVA WAY. | | | | | | ORIGINAL COMMENTS WERE ADDRESSED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|