2006-06-30 00:00:00DENIED:
  
 1.PLAN SHEETS M1, M3, M4 INDICATES 3
 DUCT RISERS WITH FIRE DAMPERS LOCATED AT
 EACH FLOOR LEVEL (1-3).PER 2004 FMC
 607.6.1, WHEN A DUCT SYSTEM PENETRATES
 NOT MORE THAN TWO STORIES, PENETRATION
 MAY BE PROTECTED BY FIRE DAMPERS AT EACH
 FLOOR LEVEL.PLANS INDICATE DUCT
 PENETRATING THREE FLOORS THEREFORE DOES
 NOT MEET THE REQUIREMENT.PLEASE
 PROVIDE A SHAFT FOR THE THREE SETS OF
 DUCT RISERS.
  
 2.PLAN SHEET M7 THE RISER DIAGRAM DOES
 NOT CORRELATE WITH THE PLAN SHEETS M1,
 M3, & M4.THE RISER DIAGRAM ONLY
 INDICATES 2 FLOORS AND NOT 3.
  
 3.PLANS DO NOT HAVE THE PROPER ADDRESS
 OF THE PORJECT WHICH IS 1920 WEKIVA WAY.
  
 ORIGINAL COMMENTS WERE ADDRESSED.
  