2006-06-20 00:00:001. NFPA 241 IS APPLICABLE TO
 CONSTRUCTION PROJECTS. YOUR PERMIT
 RESPONSE 01 IS INCORRECT.
  
 2. ALL FIRE DAMPERS WHEN INSTALLED SHALL
 BE DROP TESTED TO ENSURE PROPER
 FUNCTION.
  
 3. THE TACTILE SIGNAGE REQUIRED SHALL BE
 INSTALLED OUTSIDE THE STAIRWELL DOORS.
 THE REVISION CLOUDS SEEM TO SUGGEST
 ANOTHER LOCATION.
  
 4. ELEVATOR WARNING SIGNS SHALL BE
 PLACED DIRECTLY NEXT TO THE ELEVATOR
 CALL BUTTONS TO CALL FOR THE ELEVATOR
 CABS.
  