| 2006-06-20 00:00:00 | 1. NFPA 241 IS APPLICABLE TO | | | CONSTRUCTION PROJECTS. YOUR PERMIT | | | RESPONSE 01 IS INCORRECT. | | | | | | 2. ALL FIRE DAMPERS WHEN INSTALLED SHALL | | | BE DROP TESTED TO ENSURE PROPER | | | FUNCTION. | | | | | | 3. THE TACTILE SIGNAGE REQUIRED SHALL BE | | | INSTALLED OUTSIDE THE STAIRWELL DOORS. | | | THE REVISION CLOUDS SEEM TO SUGGEST | | | ANOTHER LOCATION. | | | | | | 4. ELEVATOR WARNING SIGNS SHALL BE | | | PLACED DIRECTLY NEXT TO THE ELEVATOR | | | CALL BUTTONS TO CALL FOR THE ELEVATOR | | | CABS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|