| 2006-06-10 00:00:00 | ****** UNSAT2ND REVIEW ****** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL APPLY AS WELL AS NEW NOTES |
| | DUE TO CHANGES IN PLANS SUBMITTED. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW WITH NEW |
| | ADDED AT BOTTOM. |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE:NO, PLEASE SEE ADDRESSING ON |
| | PLANS HAS STILL NOT BEEN ADDRESSED. THE |
| | ADDRESSING REVIEWER AND THE CITY HAS |
| | DESIGNATED THE ADDRESS OF 1920 WEKIVA |
| | WAY. NO CHNAGES HAS BEEN MADE AS OF THIS |
| | REVIEW FROM THE ADDRESSING STAFF, |
| | IN EITHER CASE BUILDING ADDRESS IS |
| | REQUIRED ON PLANS AND "THE ROAD NAME" IS |
| | NOT ADEQUATE. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE BE SURE ADDRESSING FOR |
| | LOCATION OF PROJECT IS LISTED ON TITLE |
| | BLOCKS FOR PROJECT. |
| | PLEASE SEE NOTES FORTH COMING FROM |
| | "ADDRESSING REVIEWER" |
| | |
| | 3)NOTE: OK |
| | |
| | 4)NOTE:NOTE #4 YES AND NO?, PLEASE SEE |
| | THE PHOTO-METRICS WERE SUBMITTED UNDER |
| | NORMAL, HOWEVER COULD NOT LOCATE THE |
| | LEVELS UNDER EMERGENCY? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE A "PHOTOMETRICS" |
| | FOR STAIRWAYS. PLEASE SEE 2003 NFPA-101 |
| | WHICH NOW REQUIRES A MIN OF 10FT |
| | CANDLES(108)LUX DURING NORMAL POWER AND |
| | IS PERMITTED TO 1FT CANDLE/10.8 LUX |
| | DURING EM POWER. |
| | 7.8.1.3,7.9.2.2 |
| | THIS PHOTOMETRICS DETAIL CAN BEA |
| | TYPICAL DETAIL FOR STAIRS. |
| | |
| | 5)NOTE:OK. |
| | |
| | 6)NOTE: NOTE #6 NO, RESPONSE MENTIONS |
| | THIS AS DONE, HOWEVER PLEASE SEE PLANS |
| | INDICATE BOTH THE LIGHTING ON WITH OTHER |
| | COMMON AREAS AND RECEPTS ON WITH HALL |
| | RECEPTS? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 620.23 FOR THE |
| | REQUIRED DEDICATED BRANCH CIRCUIT FOR |
| | ELEVATOR EQUIPMENT RM. |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE: OK. |
| | |
| | 9)NOTE: OK. |
| | |
| | 10)NOTE: NOTE #10 NO, PLEASE SEE FBC |
| | CHAPTER 13. THERE ARE MANY NEW |
| | REQUIREMENTS WHICH WILL AFFECT THE |
| | ELECTRICAL AS SHOWN ON PLANS. |
| | PLEASE SEE 13-415.1.ABC.1.1, |
| | 13-415.1.ABC.1.2, .1.3, ETC ETC. |
| | PLEASE SEE EACH FLR SHALL CONTAIN A |
| | SEPARATE MEANS FOR CONTROL. PLEASE SEE |
| | EACH ROOM SEPARATED BY FLR/ CEILING |
| | PARTITIONS SHALL CONTAIN AN OVER RIDE |
| | SWITCH/DEVICE WHICH PERMITS NO MORE THAN |
| | 4HRS OR 30MINS DEPENDING ON SYSTEM AND |
| | DEVICES USED. |
| | THE SCHEDULING SHALL BE INDICATED. |
| | THE DEVICES AND TIMES SHALL BE INCLUDED |
| | AND NOTED. |
| | PLEASE SEE ALL INFORMATION IN CHAPTER |
| | 13. |
| | PLEASE PROVIDE WORST CASE VOLTAGE DROP |
| | CALCUALTIONS ON PLANS FOR FEEDERS AND |
| | BRANCH CIRCUITS. 13-413.1ABC.1 |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE FBC CHAPTER 13, |
| | 13-415.ABC.1.1, 13-415.1.AB.1, ETC |
| | |
| | 11)NOTE: NOTE #11 NO, PLEASE SEE |
| | CALCUALTIONS SHALL BE CLEARLY INDICATE |
| | ON PLANS. THE MANUFACTURES SPECS |
| | SUBMITTED ARE NOT ENOUGH UNLESS THIS |
| | CONTAIN THE CALCS AND ARE SIGNED, DATED |
| | AND SEALED WITH THE TITLE BLOCK OF THE |
| | SAID ENGINEER RESPONSIBLE FOR DESIGNA DN |
| | CALCS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT WIND LOAD CALCULATIONS |
| | FOR SITE LIGHTING POLES. |
| | CALCULATIONS ARE REQUIRED IF POLES ARE |
| | GOING TO BE PERMITTED UNDER BLDG. |
| | CALCS WILL BE REVIEWED BY BLDG WHEN |
| | SUBMITTED. |
| | |
| | ************************************ |
| | NEW NOTES> |
| | |
| | 12) NOTE: PLEASE SEE PLANS REFLECT A |
| | 2002 LIFE SAFETY CODE. PLEASE SEE THE |
| | PLANS ARCHITECTURAL AND ENGINEERED PLASN |
| | SHALL INDICATE THE FOLLOWING. |
| | NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| | 2002 AT A MIN. |
| | |
| | 13) NOTE: PLEASE SEE AN "EM NOTE#1" WAS |
| | ADDED TO MANY AREAS OF PLANS WHICH IS |
| | OK, HOWEVER PLEASE SEE THIS WAS ALSO |
| | ADDED TO STAIR LOCATIONS FOR EGRESS |
| | LIGHTING FIXTURES?? |
| | PLEASE EXPLAIN AND CALRIFY THIS. ARE THE |
| | STAIR TOWER BEING PROPOSED AS PART OF |
| | THE SWITCHING FOR CHAPTER 13? |
| | IF SO, MOTION SENSORS WILL BE REQUIRED |
| | ON EACH LEVEL AND A MIN AMOUNT OF |
| | LIGHTING WILL BE REQUIRED TO BE "ON" AT |
| | ALL TIMES TO ALLEAVIATE ANY FAILURE OF A |
| | MOTION DEVICE LEAVING ANY EGRESS AREA IN |
| | TOTAL DARKNESS. |
| | |
| | 14) NOTE: PLEASE SEE FIXTURE SCHEDULE |
| | SHALL CLEARLY INDICATE ALL EM FIXTURES |
| | WITH THE REQUIRED BATTERY BACK ETC. |
| | A, B, C,,, |
| | 215.5 |
| | |
| | 15) NOTE: PLEASE SEE E-1 LT FIXTURE |
| | SCHEDULE NOTS ON LOWER LEFT HAND CORNER |
| | WHICH REFERENCES "PALM BEACH COUNTY" |
| | REQUIEMENTS. PLEASE KNOW, JOBSITE |
| | LOCATION IS NOW ANNEXED INTO THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | 16) NOTE: PLEASE SEE THE ATTACHED COPY |
| | OF FLORIDA STATUES 553.80(2)(B) WHICH IS |
| | NOW GIVEN ONLY AS A NOTICE WITH RESPECT |
| | TO REPEAT COMMENTS. |
| | |
| | ** PLEASE BE SURE TO SEE OTHER COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERTTHE NEW REVISED SHEETS |
| | INOT THE COMPLETED SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE COPY OF ALL OLD VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |