Plan Review Notes
Plan Review Notes For Permit 06010576
Permit Number 06010576
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-10 00:00:00****** UNSAT2ND REVIEW ******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL APPLY AS WELL AS NEW NOTES
 DUE TO CHANGES IN PLANS SUBMITTED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH NEW
 ADDED AT BOTTOM.
  
 1)NOTE: OK.
  
 2)NOTE:NO, PLEASE SEE ADDRESSING ON
 PLANS HAS STILL NOT BEEN ADDRESSED. THE
 ADDRESSING REVIEWER AND THE CITY HAS
 DESIGNATED THE ADDRESS OF 1920 WEKIVA
 WAY. NO CHNAGES HAS BEEN MADE AS OF THIS
 REVIEW FROM THE ADDRESSING STAFF,
 IN EITHER CASE BUILDING ADDRESS IS
 REQUIRED ON PLANS AND "THE ROAD NAME" IS
 NOT ADEQUATE.
  
 ** PREVIOUS NOTE**
 PLEASE BE SURE ADDRESSING FOR
 LOCATION OF PROJECT IS LISTED ON TITLE
 BLOCKS FOR PROJECT.
 PLEASE SEE NOTES FORTH COMING FROM
 "ADDRESSING REVIEWER"
  
 3)NOTE: OK
  
 4)NOTE:NOTE #4 YES AND NO?, PLEASE SEE
 THE PHOTO-METRICS WERE SUBMITTED UNDER
 NORMAL, HOWEVER COULD NOT LOCATE THE
 LEVELS UNDER EMERGENCY?
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE A "PHOTOMETRICS"
 FOR STAIRWAYS. PLEASE SEE 2003 NFPA-101
 WHICH NOW REQUIRES A MIN OF 10FT
 CANDLES(108)LUX DURING NORMAL POWER AND
 IS PERMITTED TO 1FT CANDLE/10.8 LUX
 DURING EM POWER.
 7.8.1.3,7.9.2.2
 THIS PHOTOMETRICS DETAIL CAN BEA
 TYPICAL DETAIL FOR STAIRS.
  
 5)NOTE:OK.
  
 6)NOTE: NOTE #6 NO, RESPONSE MENTIONS
 THIS AS DONE, HOWEVER PLEASE SEE PLANS
 INDICATE BOTH THE LIGHTING ON WITH OTHER
 COMMON AREAS AND RECEPTS ON WITH HALL
 RECEPTS?
  
 ** PREVIOUS NOTE **
 PLEASE SEE 620.23 FOR THE
 REQUIRED DEDICATED BRANCH CIRCUIT FOR
 ELEVATOR EQUIPMENT RM.
  
 7)NOTE: OK.
  
 8)NOTE: OK.
  
 9)NOTE: OK.
  
 10)NOTE: NOTE #10 NO, PLEASE SEE FBC
 CHAPTER 13. THERE ARE MANY NEW
 REQUIREMENTS WHICH WILL AFFECT THE
 ELECTRICAL AS SHOWN ON PLANS.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, .1.3, ETC ETC.
 PLEASE SEE EACH FLR SHALL CONTAIN A
 SEPARATE MEANS FOR CONTROL. PLEASE SEE
 EACH ROOM SEPARATED BY FLR/ CEILING
 PARTITIONS SHALL CONTAIN AN OVER RIDE
 SWITCH/DEVICE WHICH PERMITS NO MORE THAN
 4HRS OR 30MINS DEPENDING ON SYSTEM AND
 DEVICES USED.
 THE SCHEDULING SHALL BE INDICATED.
 THE DEVICES AND TIMES SHALL BE INCLUDED
 AND NOTED.
 PLEASE SEE ALL INFORMATION IN CHAPTER
 13.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP
 CALCUALTIONS ON PLANS FOR FEEDERS AND
 BRANCH CIRCUITS. 13-413.1ABC.1
  
 ** PREVIOUS NOTE **
 PLEASE SEE FBC CHAPTER 13,
 13-415.ABC.1.1, 13-415.1.AB.1, ETC
  
 11)NOTE: NOTE #11 NO, PLEASE SEE
 CALCUALTIONS SHALL BE CLEARLY INDICATE
 ON PLANS. THE MANUFACTURES SPECS
 SUBMITTED ARE NOT ENOUGH UNLESS THIS
 CONTAIN THE CALCS AND ARE SIGNED, DATED
 AND SEALED WITH THE TITLE BLOCK OF THE
 SAID ENGINEER RESPONSIBLE FOR DESIGNA DN
 CALCS.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT WIND LOAD CALCULATIONS
 FOR SITE LIGHTING POLES.
 CALCULATIONS ARE REQUIRED IF POLES ARE
 GOING TO BE PERMITTED UNDER BLDG.
 CALCS WILL BE REVIEWED BY BLDG WHEN
 SUBMITTED.
  
 ************************************
 NEW NOTES>
  
 12) NOTE: PLEASE SEE PLANS REFLECT A
 2002 LIFE SAFETY CODE. PLEASE SEE THE
 PLANS ARCHITECTURAL AND ENGINEERED PLASN
 SHALL INDICATE THE FOLLOWING.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002 AT A MIN.
  
 13) NOTE: PLEASE SEE AN "EM NOTE#1" WAS
 ADDED TO MANY AREAS OF PLANS WHICH IS
 OK, HOWEVER PLEASE SEE THIS WAS ALSO
 ADDED TO STAIR LOCATIONS FOR EGRESS
 LIGHTING FIXTURES??
 PLEASE EXPLAIN AND CALRIFY THIS. ARE THE
 STAIR TOWER BEING PROPOSED AS PART OF
 THE SWITCHING FOR CHAPTER 13?
 IF SO, MOTION SENSORS WILL BE REQUIRED
 ON EACH LEVEL AND A MIN AMOUNT OF
 LIGHTING WILL BE REQUIRED TO BE "ON" AT
 ALL TIMES TO ALLEAVIATE ANY FAILURE OF A
 MOTION DEVICE LEAVING ANY EGRESS AREA IN
 TOTAL DARKNESS.
  
 14) NOTE: PLEASE SEE FIXTURE SCHEDULE
 SHALL CLEARLY INDICATE ALL EM FIXTURES
 WITH THE REQUIRED BATTERY BACK ETC.
 A, B, C,,,
 215.5
  
 15) NOTE: PLEASE SEE E-1 LT FIXTURE
 SCHEDULE NOTS ON LOWER LEFT HAND CORNER
 WHICH REFERENCES "PALM BEACH COUNTY"
 REQUIEMENTS. PLEASE KNOW, JOBSITE
 LOCATION IS NOW ANNEXED INTO THE CITY OF
 WEST PALM BEACH.
  
 16) NOTE: PLEASE SEE THE ATTACHED COPY
 OF FLORIDA STATUES 553.80(2)(B) WHICH IS
 NOW GIVEN ONLY AS A NOTICE WITH RESPECT
 TO REPEAT COMMENTS.
  
 ** PLEASE BE SURE TO SEE OTHER COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERTTHE NEW REVISED SHEETS
 INOT THE COMPLETED SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF ALL OLD VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]