| 2006-03-15 00:00:00 | DENIED: |
| | 1.PLAN SHEET ME1 PLAN INDICATES IV-1, |
| | IV2, EV-1 & EV2.PLAN SHEET M7 THE |
| | BUILDING EXHAUST RISER CORRELATES WITH |
| | PLAN SHEET ME1.THE GRAVITY VENTILATOR |
| | SCHEDULE INDICATES RV-1 & 2, IV-1 & 2, |
| | PLEASE CLARIFY. |
| | |
| | 2.PLAN SHEET ME1, NOTE 1, MOUNT THE |
| | NOTED RECEPTACLE ON THE ROOF EQUIPMENT |
| | STRUCTURE.IS THIS EQUIPMENT FUTURE |
| | CONDENSING UNITS?PLEASE CLARIFY. |
| | |
| | 3.PLAN SHEET M1, 3, & 4, DUCTS |
| | PENETRATING THE RATED PARTITIONS SHALL |
| | BE PROTECTED WITH APPROVED FIRE DAMPERS |
| | OR COMPLY WITH 2004 FMC 607.5.3 |
| | EXCEPTION #2, THE DUCT SYSTEM IS |
| | CONSTRUCTED OF APPROVED MATERIALS IN |
| | ACCORDANCE WITH THIS CODE AND THE DUCT |
| | PENETRATING THE WALL MEETS ALL OF THE |
| | FOLLOWING MINIMUM REQUIREMENTS: |
| | |
| | 2.1 DUCT SHALL NOT EXCEED 100 SQUARE |
| | INCHES. |
| | 2.2 DUCT SHALL BE CONSTRUCTED IF STEEL A |
| | MINIMUM OF .0217 INCH THICKNESS. |
| | 2.3 DUCT SHALL NOT HAVE OPENINGS THAT |
| | COMMUNICATE THE COORIDOR WITH |
| | ADJACENT SPACES OR ROOMS. |
| | 2.4 DUCT SHALL BE INSTALLED ABOVE THE |
| | CEILING. |
| | 2.5 DUCT SHALL NOT TERMINATE AT A WALL |
| | REGISTER IN THE FIRE RESISTANCE |
| | RATED WALL. |
| | 2.6 A MINIMUM 12" LONG BY .060" THICK |
| | STEEL SLEEVE SHALL BE CENTERED IN |
| | EACH DUCT OPENING. THE SLEEVE SHALL |
| | BE SECURED TO BOTH SIDES OF THE WALL |
| | |
| | & ALL FOUR SIDES OF THE SLEEVE WITH |
| | MINIMUM 1 1/2" X 1 1/2" X .060" |
| | STEEL RETAINING ANGLES. THE |
| | RETAINING ANGLES SHALL BE SECURED TO |
| | |
| | THE SLEEVE & THE WALL WITH # 10 (M5) |
| | SCREWS. THE ANNULAR SPACE BETWEEN |
| | THE STEEL SLEEVE & THE WALL OPENING |
| | SHALL BE FILLED WITH ROCK (MINERAL) |
| | WOOL BATTING ON ALL SIDES. |
| | PLEASE NOTE, ITEM 2.3 APPEARS TO NOT BE |
| | IN COMPLIANCE WITH THE CODE. |
| | |
| | 4.PLAN SHEET M6 ROOF CURB SHALL BE A |
| | MINIMUM OF 8" ABOVE THE ROOF SURFACE. |
| | CONDENSING UNIT STANDS SHALL COMPLY WITH |
| | 2004 FMC TABLE 1509.7. |
| | |
| | 5.PLAN SHEET M6 PROVIDES A DETAIL FOR |
| | A FIRE DAMPER THROUGH A PARTITION BUT |
| | DOES NOT PROVIDE A DETAIL FOR THE FLOOR |
| | (HORIZONTAL) ASSEMBLY.PLEASE PROVIDE |
| | THE SPECIFIC FIRE DAMPER INSTALLATION |
| | INSTRUCTIONS ON THE JOBSITE FOR |
| | INSPECTION. |
| | |
| | 6.PLEASE PROVIDE SUBMITTAL DATA FOR |
| | THE ENERGY RECOVERY VENTILATOR & THE |
| | GRAVITY VENTILATOR. |
| | |
| | 7.PROVIDE OUTSIDE AIR CALUCALTIONS IN |
| | ACCORDANCE WITH 2004 FMC TABLE 403.3. |
| | |
| | 8.PLAN SHEET M5 BUILDING PLUMBING |
| | RISER,PLEASE CLARIFY RISER C1 - C6, |
| | ARE THESE CONDENSATE? |
| | |