Plan Review Notes
Plan Review Notes For Permit 06010576
Permit Number 06010576
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-15 00:00:00DENIED:
 1.PLAN SHEET ME1 PLAN INDICATES IV-1,
 IV2, EV-1 & EV2.PLAN SHEET M7 THE
 BUILDING EXHAUST RISER CORRELATES WITH
 PLAN SHEET ME1.THE GRAVITY VENTILATOR
 SCHEDULE INDICATES RV-1 & 2, IV-1 & 2,
 PLEASE CLARIFY.
  
 2.PLAN SHEET ME1, NOTE 1, MOUNT THE
 NOTED RECEPTACLE ON THE ROOF EQUIPMENT
 STRUCTURE.IS THIS EQUIPMENT FUTURE
 CONDENSING UNITS?PLEASE CLARIFY.
  
 3.PLAN SHEET M1, 3, & 4, DUCTS
 PENETRATING THE RATED PARTITIONS SHALL
 BE PROTECTED WITH APPROVED FIRE DAMPERS
 OR COMPLY WITH 2004 FMC 607.5.3
 EXCEPTION #2, THE DUCT SYSTEM IS
 CONSTRUCTED OF APPROVED MATERIALS IN
 ACCORDANCE WITH THIS CODE AND THE DUCT
 PENETRATING THE WALL MEETS ALL OF THE
 FOLLOWING MINIMUM REQUIREMENTS:
  
 2.1 DUCT SHALL NOT EXCEED 100 SQUARE
 INCHES.
 2.2 DUCT SHALL BE CONSTRUCTED IF STEEL A
 MINIMUM OF .0217 INCH THICKNESS.
 2.3 DUCT SHALL NOT HAVE OPENINGS THAT
 COMMUNICATE THE COORIDOR WITH
 ADJACENT SPACES OR ROOMS.
 2.4 DUCT SHALL BE INSTALLED ABOVE THE
 CEILING.
 2.5 DUCT SHALL NOT TERMINATE AT A WALL
 REGISTER IN THE FIRE RESISTANCE
 RATED WALL.
 2.6 A MINIMUM 12" LONG BY .060" THICK
 STEEL SLEEVE SHALL BE CENTERED IN
 EACH DUCT OPENING. THE SLEEVE SHALL
 BE SECURED TO BOTH SIDES OF THE WALL
  
 & ALL FOUR SIDES OF THE SLEEVE WITH
 MINIMUM 1 1/2" X 1 1/2" X .060"
 STEEL RETAINING ANGLES. THE
 RETAINING ANGLES SHALL BE SECURED TO
  
 THE SLEEVE & THE WALL WITH # 10 (M5)
 SCREWS. THE ANNULAR SPACE BETWEEN
 THE STEEL SLEEVE & THE WALL OPENING
 SHALL BE FILLED WITH ROCK (MINERAL)
 WOOL BATTING ON ALL SIDES.
 PLEASE NOTE, ITEM 2.3 APPEARS TO NOT BE
 IN COMPLIANCE WITH THE CODE.
  
 4.PLAN SHEET M6 ROOF CURB SHALL BE A
 MINIMUM OF 8" ABOVE THE ROOF SURFACE.
 CONDENSING UNIT STANDS SHALL COMPLY WITH
 2004 FMC TABLE 1509.7.
  
 5.PLAN SHEET M6 PROVIDES A DETAIL FOR
 A FIRE DAMPER THROUGH A PARTITION BUT
 DOES NOT PROVIDE A DETAIL FOR THE FLOOR
 (HORIZONTAL) ASSEMBLY.PLEASE PROVIDE
 THE SPECIFIC FIRE DAMPER INSTALLATION
 INSTRUCTIONS ON THE JOBSITE FOR
 INSPECTION.
  
 6.PLEASE PROVIDE SUBMITTAL DATA FOR
 THE ENERGY RECOVERY VENTILATOR & THE
 GRAVITY VENTILATOR.
  
 7.PROVIDE OUTSIDE AIR CALUCALTIONS IN
 ACCORDANCE WITH 2004 FMC TABLE 403.3.
  
 8.PLAN SHEET M5 BUILDING PLUMBING
 RISER,PLEASE CLARIFY RISER C1 - C6,
 ARE THESE CONDENSATE?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  