Plan Review Notes
Plan Review Notes For Permit 06010576
Permit Number 06010576
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-02-16 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. EXIT STAIRS SHALL BE KEPT UP WITH
 CONSTRUCTION.
  
 3. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 4. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 5. PROPOSED FIRE HYDRANT LOCATED IN
 PARKING AREA SHALL COMPLY WITH CITY
 UTILITY AND FIRE RESCUE STANDARDS.
  
 6. BUILDING IS REQUIRED TO BE FIRE
 SPRINKLER PROTECTED IN ACCORDANCE WITH
 FS 553.895 (2).
  
 7. A KNOX-BOX WILL BE REQUIRED. (WPB)
  
 8. TAMPER SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 9. TACTILE SIGNAGE REQUIRED AT EXIT
 DOORS.
  
 10. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 11. A STANDPIPE SYSTEM IS REQUIRED.
  
 12. THE BUILDING OVERHANG IS SHOWN AT
 13'.FIRE RESCUE NEEDS 13'-6" TO BE ABLE
 TO PASS UNDERNEATH IT.
  
 13.PLEASE INDICATE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 14. BUILDING OVERHANG WILL BE REQUIRED
 TO BE FIRE SPRINKLER PROTECTED.
  
 15. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 16. IN THE FUTURE WHEN TENANT SPACES ARE
 LEASED THEY SHALL BE PROVIDED WITH EXIT
 SIGNS, EMERGENCY LIGHTS, AND FIRE ALARM
 EQUIPMENT.
  
 17. SEPERATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM SYSTEM. THE FIRE
 ALARM SYSTEM WILL BE REQUIRED TO
 MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE.
  
 18. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
 NO FIRE SPRINKLER SYSTEM PLANS PROVIDED
 WITH DRAWINGS.
  
 19. PLEASE ILLUSTRATE FIRE EXTINGUISHER
 LOCATIONS.
  
 20. PLEASE PROVIDE VERIFICATION THAT THE
  
 PALM BEACH COUNTY 911 OFFICE HAS BEEN
 NOTIFIED FOR PROPER INCLUSION OF THIS
 ADDRESS IN THE CITY OF WEST PALM BEACH.
  
 21. HOW WILL POLICE AND FIRE RESCUE
 LOCATE THIS ADDRESS SINCE IT IS PLANNED
 TO BE ADDRESSED OFF OF OKEECHOBEE BLVD.,
 BUT IT DOES NOT FRONT THIS STREET.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709
  