Text |
| 2006-02-14 00:00:00 | ****** UNSAT ****** |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW NOTES AS |
| | "S" SHEETS ARE SEALED "PHOTO-COPIES" OF |
| | ENGINEER'S SIGNATURE. MUST BE ORIGINAL |
| | SIGNATURE PER FS 471.025 |
| | THIS COMMENT IS NOT FOR CHANE ENG. |
| | |
| | 2)NOTE: PLEASE BE SURE ADDRESSING FOR |
| | LOCATION OF PROJECT IS LISTED ON TITLE |
| | BLOCKS FOR PROJECT. |
| | PLEASE SEE NOTES FORTH COMING FROM |
| | "ADDRESSING REVIEWER" |
| | |
| | 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | AS LOCATION OF FACP SEEMS TO SHOW |
| | INTERFERENCE WITH DOOR AND DOOR SWING. |
| | PLEASE SEE THE INWARD SWING OF THIS DOOR |
| | MAY DAMAGE EQUIPMENT AS WELL AS CONTROL |
| | OR OPERATION OF PANEL AND DOOR DURING AN |
| | EMERGENCY. ** PLEASE SEE IF PERHAPS THE |
| | DOOR SWING CAN BE "OUTWARD" AS OTHER |
| | TENANT DOORS ARE SHOWN. PLEASE SEE ANY |
| | BLDG COMMENTS WITH RESPECT TO THE EGRESS |
| | PATH AND DOOR SWINGS. IF DOOR CAN NOT |
| | SWING OUT, THEN LOCATION MAY BE REQUIRED |
| | TO BE MOVED. 110.26 |
| | PLEASE ALSO SEE NFPA-72 4.4.1.4.2.2, .3 |
| | |
| | 4)NOTE: PLEASE PROVIDE A "PHOTOMETRICS" |
| | FOR STAIRWAYS. PLEASE SEE 2003 NFPA-101 |
| | WHICH NOW REQUIRES A MIN OF 10FT |
| | CANDLES(108)LUX DURING NORMAL POWER AND |
| | IS PERMITTED TO 1FT CNADLE/10.8 LUX |
| | DURING EM POWER. |
| | 7.8.1.3,7.9.2.2 |
| | THIS PHOTOMETRICS DETAIL CAN BEA |
| | TYPICAL DETAIL FOR STAIRS. |
| | |
| | 5)NOTE: PLEASE PROVIDE A BATTERY BACK UP |
| | FIXTURE OF SOME SORT IN THE ELECTRICAL |
| | ROOM(S) AND ELEVATOR EQUIPMENT RM. |
| | 700.16,7.8,7.9 |
| | |
| | 6)NOTE: PLEASE SEE 620.23 FOR THE |
| | REQUIRED DEDICATED BRANCH CIRCUIT FOR |
| | ELEVATOR EQUIPMENT RM. |
| | |
| | 7)NOTE: PLEASE INDICATE THE MIN AIC |
| | RATINGS FOR MAINS 2 AND 3. PLEASE SEE |
| | AIC RATINGS ARE SHOWN FOR OTHERS @ 65K. |
| | 110.9,215.5 |
| | |
| | 8)NOTE: PELASE INDICAT THE MIN GROUNDING |
| | ELECTRODE CONDUCTOR SIZE PER 250.66 |
| | COULD NOT LOCATE THE CONDUCTOR ON THE |
| | DETAIL OR RISER. |
| | 215.5 |
| | |
| | 9)NOTE: PLEASE INDICATE THE GROUNDING |
| | ATTACHMENT FOR THE PHONE AND CATV |
| | BOARDS.800.40 810. |
| | |
| | 10)NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.ABC.1.1, 13-415.1.AB.1, ETC |
| | |
| | 11)NOTE: PLEASE SUBMIT WIND LOAD |
| | CALCULATIONS FOR SITE LIGHTING POLES. |
| | CALCULATIONS ARE REQUIRED IF POLES ARE |
| | GOING TO BE PERMITTED UNDER BLDG. |
| | CALCS WILL BE REVIEWED BY BLDG WHEN |
| | SUBMITTED. |
| | |
| | |
| | ** PLEASE BE SURE TO SEE OTHER COMMENTS |
| | FROM OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERTTHE NEW REVISED SHEETS |
| | INOT THE COMPLETED SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE COPY OF ALL OLD VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |