Plan Review Notes
Plan Review Notes For Permit 06010576
Permit Number 06010576
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-14 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE SEE BLDG REVIEW NOTES AS
 "S" SHEETS ARE SEALED "PHOTO-COPIES" OF
 ENGINEER'S SIGNATURE. MUST BE ORIGINAL
 SIGNATURE PER FS 471.025
 THIS COMMENT IS NOT FOR CHANE ENG.
  
 2)NOTE: PLEASE BE SURE ADDRESSING FOR
 LOCATION OF PROJECT IS LISTED ON TITLE
 BLOCKS FOR PROJECT.
 PLEASE SEE NOTES FORTH COMING FROM
 "ADDRESSING REVIEWER"
  
 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AS LOCATION OF FACP SEEMS TO SHOW
 INTERFERENCE WITH DOOR AND DOOR SWING.
 PLEASE SEE THE INWARD SWING OF THIS DOOR
 MAY DAMAGE EQUIPMENT AS WELL AS CONTROL
 OR OPERATION OF PANEL AND DOOR DURING AN
 EMERGENCY. ** PLEASE SEE IF PERHAPS THE
 DOOR SWING CAN BE "OUTWARD" AS OTHER
 TENANT DOORS ARE SHOWN. PLEASE SEE ANY
 BLDG COMMENTS WITH RESPECT TO THE EGRESS
 PATH AND DOOR SWINGS. IF DOOR CAN NOT
 SWING OUT, THEN LOCATION MAY BE REQUIRED
 TO BE MOVED. 110.26
 PLEASE ALSO SEE NFPA-72 4.4.1.4.2.2, .3
  
 4)NOTE: PLEASE PROVIDE A "PHOTOMETRICS"
 FOR STAIRWAYS. PLEASE SEE 2003 NFPA-101
 WHICH NOW REQUIRES A MIN OF 10FT
 CANDLES(108)LUX DURING NORMAL POWER AND
 IS PERMITTED TO 1FT CNADLE/10.8 LUX
 DURING EM POWER.
 7.8.1.3,7.9.2.2
 THIS PHOTOMETRICS DETAIL CAN BEA
 TYPICAL DETAIL FOR STAIRS.
  
 5)NOTE: PLEASE PROVIDE A BATTERY BACK UP
 FIXTURE OF SOME SORT IN THE ELECTRICAL
 ROOM(S) AND ELEVATOR EQUIPMENT RM.
 700.16,7.8,7.9
  
 6)NOTE: PLEASE SEE 620.23 FOR THE
 REQUIRED DEDICATED BRANCH CIRCUIT FOR
 ELEVATOR EQUIPMENT RM.
  
 7)NOTE: PLEASE INDICATE THE MIN AIC
 RATINGS FOR MAINS 2 AND 3. PLEASE SEE
 AIC RATINGS ARE SHOWN FOR OTHERS @ 65K.
 110.9,215.5
  
 8)NOTE: PELASE INDICAT THE MIN GROUNDING
 ELECTRODE CONDUCTOR SIZE PER 250.66
 COULD NOT LOCATE THE CONDUCTOR ON THE
 DETAIL OR RISER.
 215.5
  
 9)NOTE: PLEASE INDICATE THE GROUNDING
 ATTACHMENT FOR THE PHONE AND CATV
 BOARDS.800.40 810.
  
 10)NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.ABC.1.1, 13-415.1.AB.1, ETC
  
 11)NOTE: PLEASE SUBMIT WIND LOAD
 CALCULATIONS FOR SITE LIGHTING POLES.
 CALCULATIONS ARE REQUIRED IF POLES ARE
 GOING TO BE PERMITTED UNDER BLDG.
 CALCS WILL BE REVIEWED BY BLDG WHEN
 SUBMITTED.
  
  
 ** PLEASE BE SURE TO SEE OTHER COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERTTHE NEW REVISED SHEETS
 INOT THE COMPLETED SETS FOR REVIEW AND
 STAMPING.
 ONE COPY OF ALL OLD VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]