Plan Review Notes
Plan Review Notes For Permit 06010576
Permit Number 06010576
Review Stop B
Sequence Number 1
Notes
Date Text
2006-04-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06010576
 ADD: 7300 OKEECHOBEE BLVD.
 CONT: ANDERSON- MOORE CONSTRUCTION
 TEL: (561)662-1819
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICA TION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PERMIT APPLICATION INDICATES PEOPERTY
 AS 7300 OKEECHOBEE BLVD WHEREAS CIVIL
 SHEETS INDICATE A PRIVATE NAMED ROAD
 WAKEVIA WAY PROPERTY SHOULD HAVE AN
 ADDRESS OFF OF WAKEVIA WAY. SEE
 ADDRESSING TECHNITION LILI URSA FOR
 NEWLY ASSIGNED ADDRESS. (561)805-6731.
  
 4)PROVIDE 3 SOILS REPORTS SIGNED AND
 SEALED.1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH
 1802.6 .
  
 5) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 6)13-101.1.6 SHELL BUILDINGS.
 NONRESIDENTIAL BUILDINGS THAT ARE
 PERMITTED PRIOR TO DESIGN COMPLETION OR
 WHICH WILL BE FINISHED IN SECTIONS AT A
 TIME AFTER CONSTRUCTION OF THE SHELL
 SHALL COMPLY WITH EITHER METHOD B OR C
 OF SUBCHAPTER 13-4 OF THE CODE PRIOR TO
 GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT
 INSTALLED UNTIL LATER THAT ARE NOT ON
 THE BUILDING PLANS SHALL BE LISTED AND
 APPENDED TO THE COMPLIANCE FORM
 SUBMITTED TO THE BUILDING DEPARTMENT.
 UNLESS THE BUILDING IS COMPLETED AS PER
 ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED
 CODE SUBMITTAL(S) USING METHODS A, B OR
 C SHALL BE SUBMITTED WHEN COMPLETION OF
 THE BUILDING (OR PART OF THE BUILDING)
 IS PERMITTED.
  
 7) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 8) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 9) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF FLOORS
 H) SQ. FT. FOOTPRINT
 I) SQ. FT. UNDER ROOF (TOTAL)
 J) OCCUPANT LOAD
 K) FLOOD ZONE
 L) FLOOD ELEVATION
 M)L.O.M.R.LETTER OF MAP REVISION
  
 10) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 11) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) SHEET 1.1 CODE SUMMARY INDICATES THE
 DESIGNER HAS DECLARED THIS A TYPE VB/
 BUSINESS, BUILDING WITH AREA AND HEIGHT
 MODIFICATIONS. PLEASE PROVIDE THE
 CALCULATIONS FOR FRONTAGE INCREASE 506.2
 AND AREA MODICATIONS 506.1 AND 506.3
 AUTOMATIC SPRINKLER SYSTEM INCREASE.
  
 14) PLEASE PROVIDE SITE PLAN WITH THE
 ACCCESSIBLE ROUTE TO THE PUBLIC WAY.
 11-4.1.2;
 (1) AT LEAST ONE ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 SHALL BE
 PROVIDED WITHIN THE BOUNDARY OF THE SITE
 FROM PUBLIC TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER
 LOADING ZONES IF PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
 (2) AT LEAST ONE ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE
 FACILITIES, ACCESSIBLE ELEMENTS, AND
 ACCESSIBLE SPACES THAT ARE ON THE SAME
 SITE.
  
 15) THE PLANS DO NOT CLEARLY INDICATE
 THE ELEVATION CHANGES ON THE PASSENGER
 LOADING ZONE LOCATED ON THE WEST END OF
 THE BUILDING. CIVIL PLANS INDICATE ON
 THE WEST SIDE OF THE PORTICO A ELEVATION
 OF 17'-71/2" WHERE AS THE PLAN INDICATES
 THE INTERIOR FINISH FLOOR OF 18'-6" THIS
 IS A CHANGE OF 101/2".PLEASE PROVIDE
 SAME INFORMATION ON CHANGE IN GRADE FOR
 THE EAST ENTRY. PLEASE PROVIDE A
 SECTION THROUGH THE PASSENGER LOADING
 ZONE.11-4.6.6 PASSENGER LOADING ZONES.
  
 PASSENGER LOADING ZONES SHALL PROVIDE AN
 ACCESS AISLE AT LEAST 60 INCHES (1525
 MM) WIDE AND 20 FEET (6096 MM) LONG
 ADJACENT AND PARALLEL TO THE VEHICLE
 PULL-UP SPACE (SEE FIGURE 11-10 ). IF
 THERE ARE CURBS BETWEEN THE ACCESS AISLE
 AND THE VEHICLE PULL-UP SPACE, THEN A
 CURB RAMP COMPLYING WITH SECTION 11-4.7
 SHALL BE PROVIDED. VEHICLE STANDING
 SPACES AND ACCESS AISLES SHALL BE LEVEL
 WITH SURFACE SLOPES NOT EXCEEDING 1:50
 (2 PERCENT) IN ALL DIRECTIONS.
  
 16) SHEET 3.1 SECTIONS 3/ 6.1, DETAIL
 1/8.3 & DETAIL 1/ 8.4 STAIR SECTIONS DO
 NOT PROVIDE GUARD INFORMATION COMPLYING
 WITH:11-4.4.2 HEAD ROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AILES OR
 OTHER CIRCULATION SPACES SHALL HAVE 80
 INCHES MINIMUM CLEAR HEAD ROOM (SEE
 FIGURE 8(A)). IF VERTICAL CLEARENCE OF
 AN AREA ADJOINING AN ACCESSIBLE ROUTE IS
 REDUCED TO LESS THAN 80 IN. (NOMINAL
 DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY- IMPARED PERSONS SHALL BE
 PROVIDED. (SEE FIGURE 8(C-1)).
  
 17A) SHEET 10.1 DOOR SCHEDULE EXIT SHAFT
 ENCLOSURE DOORS TO BE 45 MINUTE RATED
 NOT 20 MIN AS CORRIDOR DOORS ARE.
  
 7.3.1 SHAFT ENCLOSURES.
 THE FIRE-RESISTANCE RATING OF THE FIRE
 BARRIER SEPARATING BUILDING AREAS FROM A
 SHAFT SHALL COMPLY WITH SECTION 707.4 .
  
 707.4
 SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN
 2 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE AND NOT LESS THAN1 HOUR WHERE
 CONNECTING LESS THAN FOUR STORIES. THE
 NUMBER OF STORIES CONNECTED BY THE SHAFT
 ENCLOSURE SHALL INCLUDE ANY BASEMENTS
 BUT NOT ANY MEZZANINES. SHAFT ENCLOSURES
 SHALL BE CONSTRUCTED AS FIRE BARRIERS IN
 ACCORDANCE WITH SECTION 706 . SHAFT
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE
 RATING NOT LESS THAN THE FLOOR ASSEMBLY
 PENETRATED, BUT NEED NOT EXCEED 2 HOURS.
  
  
 706.3.2 EXIT ENCLOSURES.
 THE FIRE-RESISTANCE RATING OF THE FIRE
 BARRIER SEPARATING BUILDING AREAS FROM
 AN EXIT SHALL COMPLY WITH SECTION 1019.1
 .
  
 1019.1 ENCLOSURES REQUIRED.
  
 INTERIOR EXIT STAIRWAYS AND INTERIOR
 EXIT RAMPS SHALL BE ENCLOSED WITH FIRE
 BARRIERS. EXIT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN
 2 HOURS WHERE CONNECTING FOUR STORIES OR
 MORE AND NOT LESS THAN 1 HOUR WHERE
 CONNECTING LESS THAN FOUR STORIES. THE
 NUMBER OF STORIES CONNECTED BY THE SHAFT
 ENCLOSURE SHALL INCLUDE ANY BASEMENTS
 BUT NOT ANY MEZZANINES. AN EXIT
 ENCLOSURE SHALL NOT BE USED FOR ANY
 PURPOSE OTHER THAN MEANS OF EGRESS.
 ENCLOSURES SHALL BE CONSTRUCTED AS FIRE
 BARRIERS IN ACCORDANCE WITH SECTION 706
 .
  
 715.3.4 DOORS IN VERTICAL EXIT
 ENCLOSURES AND EXIT PASSAGEWAYS.
 FIRE DOOR ASSEMBLIES IN VERTICAL EXIT
 ENCLOSURES AND EXIT PASSAGEWAYS SHALL
 HAVE A MAXIMUM TRANSMITTED TEMPERATURE
 END POINT OF NOT MORE THAN 450?F (232?C)
 ABOVE AMBIENT AT THE END OF 30 MINUTES
 OF STANDARD FIRE TEST EXPOSURE.
 SEE TABLE 715.3 FIRE BARRIERS REQUIRING
 1 HR RATING/ OPENING PROTECTIVES.
  
  
 17B) SAID DOOR SCHEDULE LIST DOORS AS
 "C" LABEL DOORS TABLE 715.3 RATES DOORS
 IN MINUTES AND HRS.
  
 17 C) DOOR# 307 NOT ON SCHEDULE.
  
 18)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLIONS
 C) GLAZED EXTERIOR DOORS
 D) EXT METAL DOORS
 E) ROOFING ASSEMBLIES
 F) PREMANUFACTURED A/C STANDS
  
 19) INFORMATION REQUIRED FOR ROOFING
 REPORTS:
 ) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
  
 20) SHEET S-8 WIND DESIGN
 20A) DESIGNED TO THE WRONG CODE, 2004
 FBC.
  
 21)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026