| 2006-01-30 00:00:00 | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS NEED TO BE ON |
| | FORM 600A-04 (2004) PER FBC 13-600.3.A . |
| | |
| | 2) ENERGY CAL'S. NEED TO BE SIGNED BY |
| | OWNER/AGENT. |
| | |
| | 3)MASTER BATH EXHAUST FAN #2 IS NOT |
| | SHOWING ON MECHANICAL PLANS PLEASE |
| | CORRECT. |
| | |
| | 4) ALL MASTER SUITE RETURN AIR GRILL |
| | SURFACE AREA'S ARE TO SMALL PLEASE |
| | CORRECT. |
| | |
| | 5) AHU #2 RETURN AIR GRILL IN HALL 8X8 |
| | SURFACE AREA IS TO SMALL. |
| | |
| | 6) RETURN AIR GRILL IN LAUNDRY IS NOT |
| | SIZED. |
| | |
| | 7) 8" RETURN AIR DUCT IN VEST. IS TO |
| | SMALL SEE NOTE #8. |
| | |
| | 8) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 9) ARCHITECT'S LICENSE NUMBER MUST BE |
| | PRINTED ON PLANS. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |
| | |
| | |