 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FIRMS CERTIFICATE OF
 AUTHORIZATION NUMBER IS REQUIRED IN THE
 TITLE BLOCK PER 61G1-16.004(2) FAC.
  
 2} THE LOAD CALCULATION INDICATES 196
 AMPS, THE "EXISTING METER/MAIN"
 INDICATES IT IS 200 AMP, NOTE #5 REFERS
 TO UPGRADING TO 150 AMPS. PLEASE
 CORRELATE, ALSO INDICATE THE SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR.
  
 3} THE NOTE REFERING TO AN EXTENDED
 "FEEDER" ON THE RISER DIAGRAM
 INDICATES THE SERVICE MAY BE MOVED, IF
 SO SHOW THE NEW LOCATION ON THE PLAN.
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR
 THIS WORK. NO CONTRACTOR IS SIGNED ON
 THE APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  