| Notes |
| Date |
Text |
| 2006-01-27 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE FIRMS CERTIFICATE OF | | | AUTHORIZATION NUMBER IS REQUIRED IN THE | | | TITLE BLOCK PER 61G1-16.004(2) FAC. | | | | | | 2} THE LOAD CALCULATION INDICATES 196 | | | AMPS, THE "EXISTING METER/MAIN" | | | INDICATES IT IS 200 AMP, NOTE #5 REFERS | | | TO UPGRADING TO 150 AMPS. PLEASE | | | CORRELATE, ALSO INDICATE THE SIZE OF THE | | | GROUNDING ELECTRODE CONDUCTOR. | | | | | | 3} THE NOTE REFERING TO AN EXTENDED | | | "FEEDER" ON THE RISER DIAGRAM | | | INDICATES THE SERVICE MAY BE MOVED, IF | | | SO SHOW THE NEW LOCATION ON THE PLAN. | | | | | | AN ELECTRICAL PERMIT IS REQUIRED FOR | | | THIS WORK. NO CONTRACTOR IS SIGNED ON | | | THE APPLICATION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|