| Plan Review Notes For Permit 06010515 |
| Permit Number |
06010515 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-08 00:00:00 | **** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE ONLY PRELIMINARY | | | A-SHEETS WERE SUIBMITTED FOR REVIEW. | | | PLEASE SEE COMPLETE PLANS WERE NOT | | | SUBMITTED FOR REVIEW OF ARCHITECTUAL, OR | | | MEP SHEETS. | | | PLEASE BE SURE TO SUBMIT COMPLETED PLANS | | | FOR CODE COMPLIANCE UNDER THE 2004 FBC. | | | PLEASE SEE FBC CHAPTER 13 FOR COMMERCIAL | | | BLDGS. THERE HAVE MANY BEEN MANY CHANGES | | | FROM THE PREVIOUS 2001 FBC CHAPTER 13. | | | | | | PLEASE ALSO SEE WE ARE CURRENTLY UNDER | | | THE 2003 NFPA-101 WHICH CONTAINS MANY | | | CHANGES FROM THE 2000 LS-101. | | | PLEASE ESP SEE 7.8.1.3,7.9.2.2 | | | COMPLETE PHOTOMETRICS WILL BE REQUIRED | | | FOR ALL EGRESS PATHS. | | | PLEASE SEE STAIR TOWERS ARE NOW REQUIED | | | TO HAVE A MIN OF 10FT CANDLES (108 LUX) | | | UNDER NORMAL POWER AND 1FT CANDLE UNDER | | | EM POWER. | | | PLEASE ALSO SEE WE ARE NOW UNDER THE | | | 2002 NFPA-72, 2002 NFPA-70 (NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|