Plan Review Notes
Plan Review Notes For Permit 06010515
Permit Number 06010515
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-08 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE ONLY PRELIMINARY
 A-SHEETS WERE SUIBMITTED FOR REVIEW.
 PLEASE SEE COMPLETE PLANS WERE NOT
 SUBMITTED FOR REVIEW OF ARCHITECTUAL, OR
 MEP SHEETS.
 PLEASE BE SURE TO SUBMIT COMPLETED PLANS
 FOR CODE COMPLIANCE UNDER THE 2004 FBC.
 PLEASE SEE FBC CHAPTER 13 FOR COMMERCIAL
 BLDGS. THERE HAVE MANY BEEN MANY CHANGES
 FROM THE PREVIOUS 2001 FBC CHAPTER 13.
  
 PLEASE ALSO SEE WE ARE CURRENTLY UNDER
 THE 2003 NFPA-101 WHICH CONTAINS MANY
 CHANGES FROM THE 2000 LS-101.
 PLEASE ESP SEE 7.8.1.3,7.9.2.2
 COMPLETE PHOTOMETRICS WILL BE REQUIRED
 FOR ALL EGRESS PATHS.
 PLEASE SEE STAIR TOWERS ARE NOW REQUIED
 TO HAVE A MIN OF 10FT CANDLES (108 LUX)
 UNDER NORMAL POWER AND 1FT CANDLE UNDER
 EM POWER.
 PLEASE ALSO SEE WE ARE NOW UNDER THE
 2002 NFPA-72, 2002 NFPA-70 (NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  