| 2006-07-05 00:00:00 | **** UNSAT **** |
| | |
| | |
| | |
| | ** |
| | 1) NOTE: PLEASE SEE THE ELECTRICAL PAGE |
| | CONTAINS "WHITE-OUT" AND HAND DRAWN |
| | CHANGES. PLEASE KNOW, IN NO CASE CAN |
| | "WHITE OUT" BE USED ON PLANS. HAND DRAWN |
| | CHANGES MAY BE DONE BY A DESIGNER OF |
| | RECORD, HOWEVER EACH AND EVERY HAND |
| | WRITTEN DETAIL OR CHANGED WOULD BE |
| | REQUIRED TO BE SIGNED/INITIALED AND |
| | DATED. |
| | PLEASE REPRINT SHEETS ALONG WITH ANY |
| | COMMENTS FROM ANY OTHER TRADES AND SIGN, |
| | DATED AND SEAL PLANS. |
| | FS 481.221. |
| | |
| | 2) NOTE: PLEASE SEE BUILDING REVIEW |
| | ADJUSTED THE VALUE FOR SCOPE PF WORK, |
| | HOWEVER THE FEES WERE NOT PAID. THESE |
| | FEES ARE REQUIRED TO BE PAID. |
| | FBC ADMIN SECT 108.3 |
| | |
| | 3) NOTE: ONE SET/COPY OF THE OLD/VOIDED |
| | SHEETS WERE NOTSUBMITTED FOR |
| | REFERENCE? |
| | PLEASE SEE THESE PLANS ARENOWMISSING |
| | THE AIC RATING OF THE SERVICE EQUIPMENT. |
| | PLEASE REVISE AND INDICATE THIS. |
| | 110.9/215.5 |
| | |
| | 4) NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN DISCONNECT |
| | TO THE SUB PANEL. |
| | 250.110.250.24B,250.122 |
| | THIS WAS NOTED ON PREVIOUS REVIEW TO |
| | INCLUDE. |
| | |
| | **PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT THE NEW REVISED SHEETS |
| | FOR REVIEW STAMPING. |
| | ONE SET OF THE OLD/VOIDED REMOVED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |