| Date |
Text |
| 2006-03-14 00:00:00 | |
| | |
| | |
| | |
| | DENIED |
| | |
| | |
| | |
| | 1) PERMIT VALUATION IS LOW, VALUATION |
| | HAS BEEN ADJUSTED TO THE AVERAGE |
| | CONSTRUCTION COSTS AS SET OUT BY ICC PER |
| | 108.3 FBC* |
| | |
| | 2) CORRECT THE FOLLOWING INFORMATION ON |
| | DRAWINGS, |
| | A) UPDATEWIND DESIGN CRITERIA TO |
| | NEW STANDARD |
| | B) BUILDING TYPE |
| | C) CONCRETE STRENGTH ON FOUNDATION |
| | NOTES AND GENERAL NOTES DIFFER |
| | D) FASTENERS DIFFER ON GARAGE DOOR BUCK |
| | DETAIL AND FASTENER SCHEDULE |
| | E) ADDRESS ON SITE PLAN A/4 IS LAKE |
| | WORTH |
| | |
| | 3) SHOW DRAINAGE ON SITE PLANS PER |
| | R401.3 FBC |
| | |
| | 4) PROVIDE SOIL REPORT PER R401.4 FBC |
| | AND ARCHITECTS GENERAL NOTES #7 |
| | |
| | 5) FOUNDATION #3 SHALL BE A MINIMUM OF |
| | 12" BELOW GRADE PER R403.1.4 FBC SHOW ON |
| | DETAIL H/2 |
| | |
| | 6) BEDROOM WINDOWS DO NOT MEET |
| | EMERGENCY EGRESS REQUIREMENTS PER R310.1 |
| | - R310.1.4 FBC SHOW COMPLIANCE |
| | |
| | 7) DOORS, WALLS, AND CEILING BETWEEN |
| | GARAGE AND DWELLING SHALL MEET THE |
| | REQUIREMENTS OF SECTION R309 FBC |
| | |
| | 8) SPECIFY BEAM/LINTEL LENGTH AND THAT |
| | THEY COMPLY WITH 2104.1.5 FBC |
| | |
| | 9) INSULATION IS REQUIRED BETWEEN |
| | GARAGE AND DWELLING (WALLS AND CEILING) |
| | PROVIDE DETAIL OR NOTES |
| | |
| | 10) SUBMIT TRUSS DRAWINGS FOR ROOF AND |
| | 2ND FLOOR PER106.1.1.2 FBC* AND |
| | R802.10.1 |
| | |
| | 11) THOSE PRODUCTS WHICH ARE REGULATED |
| | BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 12) PROVIDE CERTIFICATION LETTER FROM |
| | ATRIUM WINDOWS THAT WIND LOADS WILL BE |
| | MET FOR SH WINDOWS |
| | |
| | 13) PROVIDE A KEY PLAN AND INSTALLATION |
| | SCHEDULE SIMILAR TO ATTACHED SAMPLE ALSO |
| | SHOW ATTACHMENT TYPE, ETC. ON PRODUCT |
| | APPROVALS |
| | |
| | 14) RADON FEES SHALL BE COLLECTED FOR |
| | THE STATE OF FLORIDA PER CHAPTER 10D-91 |
| | FAC |
| | |
| | 15) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO A |
| | PERMIT BEING ISSUED |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 |
| | FBC* = WEST PALM BEACH |
| | ADMINISTATIVE AMMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |