| 2006-07-06 00:00:00 | *** DENIED *** |
| | 1) WHITE-OUT MAY NOT BE USED ON PLANS, |
| | ALL HAND MADE CHANGES MUST BE SIGNED AND |
| | DATED AT EACH CHANGE WITH-OUT USING |
| | WHITE-OUT. |
| | |
| | 2) AS SUPPLY AIR DUCT SIZES APPEAR TO BE |
| | OVER SIZED, PLEASE SUBMIT MANUAL D |
| | CALCULATIONS FOR RESIDENTIAL DUCT DESIGN |
| | OR OTHER APPROVED CALCULATIONS, PER 2004 |
| | FBC/R M1601.1 . |
| | |
| | 3) AT THIS TIME THE 14" RETURN AIR |
| | TRANSFER DUCT NEEDS TO BE 16" DUE TO THE |
| | SUPPLY AIR DUCT SIZES IN THE MASTER |
| | SUITE, SEE NOTE #4 (A) AND (C) MASTER |
| | SUITE. |
| | |
| | 4) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |