Plan Review Notes
Plan Review Notes For Permit 06010504
Permit Number 06010504
Review Stop P
Sequence Number 1
Notes
Date Text
2006-04-01 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1) SHT A2
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 2) SHT A2
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL
 (SEE ALSO SECTION 106.3.5).
 PROVIDE A DETAIL OF THE SHELF FOR THE
 WATER HEATER OVER THE CLOTHES DRYER.
  
 3) SEC 608 PROTECTION OF WATER SUPPLY.
 PROVIDE INFORMATION: WATER SUPPLY TO
 EACH UNIT, ONE METER FOR ALL UNITS,
 REQUIRE A BACK FLOW PREVENTER AT THE
 METER. LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  