| Plan Review Notes For Permit 06010504 |
| Permit Number |
06010504 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-10 00:00:00 | ******DENIED****** | | | | | | 1) STAIRS SHALL COMPLY WITH APPLICABLE | | | BUILDING CODES AND NFPA 101, 2003 | | | EDITION SECTION 7.2.2. | | | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED FOR EACH UNIT, AND MUST BE | | | MOUNTED AT TIME OF FIRE FINAL | | | INSPECTION. | | | | | | 3) ADDRESSES ARE REQUIRED FOR BUILDING, | | | AND SHALL MEET THE RESIDENTIAL | | | REQUIREMENT OF MINIMUM 3" IN HEIGHT AND | | | CONTRASTING TO BACKGROUND. | | | | | | 4) SMOKE DETECTORS TO BE PLACED A | | | MINIMUM OF (3)' FROM HVAC DIFFUSERS. | | | | | | 5) CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|