Plan Review Notes
Plan Review Notes For Permit 06010504
Permit Number 06010504
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-17 00:00:00***********UNSAT ***********
  
 1)NOTE: PLEASE SEE ALL CURRENT CODES
 SHALL BE REFERENCED.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72 AT A MIN.
  
 2)NOTE: PLEASE SEE VALUATION FOR THIS
 PROJECT IS WAY TOO LOW. THE $210K ON
 APPLICAION IF NOT ADJUSTED CORRECTLY BY
 THE CONTRACTOR, SHALL BE ADJUSTED BY
 THIS OFFICE BASED ON THE TABLES ADOTED
 INTO THE 2004 FBC.
 108.3
  
 3)NOTE: PLEASE SEE PLANS AND ELECTRICAL
 SERVICES ARE INDICATING THESE AS
 "TOWNHOMES" , WHICH AS DEFINED UNDER THE
 FBC , NEC THESE ARE NOT. PLEASE KNOW, IF
 INDEED FEE SIMPLE TH, EACH UNIT WOULD
 HAVETHEIR OWN PCN, EACH UNIT WOULD
 HAVE ITS OWN PERMIT APPLICATION ETC.
 PLEASE SEE BLDG REVIEW NOTES.
 PLEASE ALSO SEE FURTHER ELECTRICAL
 COMMENTS FOR SERVICE.
  
 4)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.(S) UNIT PANEL
 SCHEDULE(S) CNA BE TYPICAL AS EACH FLOOR
 LAYOUT APPEARS TO BE THE SAME.
 215.5
  
 5)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52
  
 6)NOTE: PLEASE SEE THERE CAN ONLY BE ONE
 ELECTRICAL SERVICE. 230.2, ALL MAINS TO
 BE GROUPED. 230.72, SIZING OF SEC'S, GE
 SYSTEMS ETC SHALL BE BASED ON
 240.4,250.66,310.16 ETC.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW SERVICE. 110.9, 215.5
  
 8)NOTE: PLEASE SEE BEDRMS WHICH INDICATE
 THE EGRESS LIGHTING AS A FUTURE FAN/LT.
 PLEASE KNOW, EITHER A SWITCHED RECEPT
 MUST BE INSTALLED, OR A LIGHTING FIXTURE
 OF SOME SORT WILL BE REQUIRED.
 LS101 7.8, 210.70
  
 9)NOTE: PLEASE CORRELATE KW RATING OF
 CU'S ON ELECTRICAL PLANS WITH MECHANICAL
 PLANS. ONE SHOWS 4.5 AND THE OTHER 7.5.
 PLEASE ALSO VERIFY THE 60A OCP FOR AHU
 AS SHOWN, THIS SEEMS A LITTLE HIGHER
 THAN NORMAL.
 424.3,215.5 ETC
  
 10)NOTE: PLEASE SEE 210.11C, 220.16 FOR
 MIN VA FOR WASHER/AND LAUNDRY CIRCUIT
 REQUIRED. 210.52F
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELETCRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  