| 2006-03-17 00:00:00 | ***********UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE ALL CURRENT CODES |
| | SHALL BE REFERENCED. |
| | 2002 NFPA-70, 2003 NFPA-101, 2002 |
| | NFPA-72 AT A MIN. |
| | |
| | 2)NOTE: PLEASE SEE VALUATION FOR THIS |
| | PROJECT IS WAY TOO LOW. THE $210K ON |
| | APPLICAION IF NOT ADJUSTED CORRECTLY BY |
| | THE CONTRACTOR, SHALL BE ADJUSTED BY |
| | THIS OFFICE BASED ON THE TABLES ADOTED |
| | INTO THE 2004 FBC. |
| | 108.3 |
| | |
| | 3)NOTE: PLEASE SEE PLANS AND ELECTRICAL |
| | SERVICES ARE INDICATING THESE AS |
| | "TOWNHOMES" , WHICH AS DEFINED UNDER THE |
| | FBC , NEC THESE ARE NOT. PLEASE KNOW, IF |
| | INDEED FEE SIMPLE TH, EACH UNIT WOULD |
| | HAVETHEIR OWN PCN, EACH UNIT WOULD |
| | HAVE ITS OWN PERMIT APPLICATION ETC. |
| | PLEASE SEE BLDG REVIEW NOTES. |
| | PLEASE ALSO SEE FURTHER ELECTRICAL |
| | COMMENTS FOR SERVICE. |
| | |
| | 4)NOTE: PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULE.(S) UNIT PANEL |
| | SCHEDULE(S) CNA BE TYPICAL AS EACH FLOOR |
| | LAYOUT APPEARS TO BE THE SAME. |
| | 215.5 |
| | |
| | 5)NOTE: PLEASE SEE SOME MISSING RECEPTS |
| | PER 210.52 |
| | |
| | 6)NOTE: PLEASE SEE THERE CAN ONLY BE ONE |
| | ELECTRICAL SERVICE. 230.2, ALL MAINS TO |
| | BE GROUPED. 230.72, SIZING OF SEC'S, GE |
| | SYSTEMS ETC SHALL BE BASED ON |
| | 240.4,250.66,310.16 ETC. |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | NEW SERVICE. 110.9, 215.5 |
| | |
| | 8)NOTE: PLEASE SEE BEDRMS WHICH INDICATE |
| | THE EGRESS LIGHTING AS A FUTURE FAN/LT. |
| | PLEASE KNOW, EITHER A SWITCHED RECEPT |
| | MUST BE INSTALLED, OR A LIGHTING FIXTURE |
| | OF SOME SORT WILL BE REQUIRED. |
| | LS101 7.8, 210.70 |
| | |
| | 9)NOTE: PLEASE CORRELATE KW RATING OF |
| | CU'S ON ELECTRICAL PLANS WITH MECHANICAL |
| | PLANS. ONE SHOWS 4.5 AND THE OTHER 7.5. |
| | PLEASE ALSO VERIFY THE 60A OCP FOR AHU |
| | AS SHOWN, THIS SEEMS A LITTLE HIGHER |
| | THAN NORMAL. |
| | 424.3,215.5 ETC |
| | |
| | 10)NOTE: PLEASE SEE 210.11C, 220.16 FOR |
| | MIN VA FOR WASHER/AND LAUNDRY CIRCUIT |
| | REQUIRED. 210.52F |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | |
| | PLEASE BE SURE TO SEE ANY COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |