| 2006-05-11 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) THE CLAIMED VALUATION ON THE PERMIT |
| | APPLICATION IS LOW. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| | COST EXCLUDING LAND VALUE. OUR VALUATION |
| | REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| | AND MEANS COST ANALYSIS SERVICES PER |
| | 108.3 FBC* PERMIT VALUE WILL BE ADJUSTED |
| | ACCORDINGLY |
| | |
| | 2) WIND DESIGN INFORMATION SHT A3 SHALL |
| | USE ASCE 7-02 STANDARD FROM 2004 FBC |
| | ALSO DRAWING SPECIFIES EXP. C AND THE |
| | COMPONENT AND CLADDING SHT IS USING 2001 |
| | CODE WITH EXP. B PLEASE CLARIFY |
| | |
| | 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT |
| | APPLICATION OR BEFORE INSTALLATION |
| | |
| | 4) THE PERMIT APPLICATION SHALL INCLUDE |
| | TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| | |
| | IS RELEVANT PER 9B-72. THESE SHOULD |
| | INCLUDE THE FLORIDA STATE APPROVAL COVER |
| | PAGES, AND THE PRODUCT NOA THAT LISTS |
| | THE SYSTEM COMPONENTS/ FASTENER LIST |
| | PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE |
| | GENERAL LIMITATIONS PAGE. ALL CAN BE |
| | FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 5) THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 6) PRODUCT APPROVAL FOR SINGLE HUNG |
| | WINDOWS DO NOT STATE DESIGN PRESSURES. |
| | THESE ARE REQUIRED FOR PRODUCT |
| | COMPLIANCE, PLEASE PROVIDE MANUFACTURERS |
| | |
| | SPECIFICATIONS FOR DESIGN PRESSURES ON |
| | THIS PRODUCT. ALSO SUPPLY THE SIZE OF |
| | THE MANUFACTURERS SH DESIGNATIONS (SH23, |
| | SH24, SH25, AND SH35) |
| | |
| | 7) MIN. FOOTING DEPTH BELOW GRADE IS 12" |
| | PER 1805.2 FBC, DETAIL K/8 ON A8 SHOW |
| | 10" ALSO FOUNDATION SCHEDULE FOR TYPE 1 |
| | FOUNDATION DOES NOT MATCH SIZE ON DETAIL |
| | K/8 ON A8 PLEASE CLARIFY |
| | |
| | 8) SECTION L/8 ON A8 HAS TWO DIFFERENT |
| | CEILING HEIGHTS PLEASE CLARIFY |
| | |
| | 9) SEE PLACEMENT OF ATTIC ACCESS ON A5 |
| | THIS LOCATION WILL NOT PROVIDEREQUIRED |
| | 30" CLEARANCE ABOVE |
| | |
| | 10) ATTIC ACCESS DETAIL D/3 ONA3 DOES |
| | NOT MEET THE MIN. WIDTH REQUIREMENT OF |
| | 20" |
| | |
| | 11) PROVIDE BEAM/LINTEL SCHEDULE WITH |
| | LENGTHS THAT MEET THE 4" MIN. BEARING |
| | PER 2104.1.5 |
| | |
| | 12) PROVIDE DRAINAGE PLAN (SHOW DRAINAGE |
| | ON SITE OR LANDSCAPE PLAN) |
| | |
| | 13) ENERGY CALC'S SHALL BE SIGNED BY |
| | OWNER/AGENT |
| | |
| | 14) FEE SIMPLE TOWNHOUSES REQUIRE |
| | SEPERATE PROPERTY CONTROL NUMBERS |
| | |
| | 15) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |