| Plan Review Notes For Permit 06010488 |
| Permit Number |
06010488 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-16 00:00:00 | ***DENIED*** | | | | | | THE RESUBMITTED PLANS NOW SHOW AN | | | OCCUPANT LOAD OF 339. SHT C | | | PLEASE SEE FIRST FIRE REVIEW COMMENT | | | REGARDING OCCUPANT LOADS. IT WAS | | | ORIGINALLY UNDERSTOOD THAT THE OCCUPANT | | | LOAD WAS BELOW 300. PLEASE NOTE THAT | | | FIRE ALARM SYSTEMS ARE REQUIRED IN | | | ACCORDANCE WITH NFPA 101, 2003 EDITION | | | WHERE OCCUPANT LOAD EXCEEDS 300. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|