2006-06-16 00:00:00***DENIED***
  
 THE RESUBMITTED PLANS NOW SHOW AN
 OCCUPANT LOAD OF 339. SHT C
 PLEASE SEE FIRST FIRE REVIEW COMMENT
 REGARDING OCCUPANT LOADS. IT WAS
 ORIGINALLY UNDERSTOOD THAT THE OCCUPANT
 LOAD WAS BELOW 300. PLEASE NOTE THAT
 FIRE ALARM SYSTEMS ARE REQUIRED IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION
 WHERE OCCUPANT LOAD EXCEEDS 300.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722