Plan Review Notes
Plan Review Notes For Permit 06010488
Permit Number 06010488
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-08 00:00:00IN REVIEW
 ******** UNSAT ********
  
 ** PLANS SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE SEE CIRCUITING FOR
 EM/EXT LTS SHALL BE CIRCUITED TO THE
 LOCAL BRANCH CIRCUIT LIGHTING IN ANY ONE
 AREA. PLEASE SEE A NOTE ON PLANS
 MENTIONS TO CIRCUIT TO LOCAL CIRCUIT
 AHEAD OF SWITCHING , HOWEVER PLEASE SEE
 THESE SEEM TO BE CIRCUITED TO DEDICATED
 CIRCUIT(S)?
 PLEASE KNOW, IF LIGHTING IN ANY ONE ARE
 GOES OUT BY SWITCHING OR TRIPPING A
 SINGLE MEANS OF OCP, THE EM LTS SHALL BE
 ACTIVATED. THIS WILL ALLEAVIATE ANY ONE
 AREA IN DARKNESS.
 700.12E,NFPA-101 7.9.2.2
  
 2) NOTE: PLEASE REFERENCE NFPA-101 2003,
 NFPA-72 2002 ON PLANS AS REQUESTED ON
 PREVIOUS REVIEW.
  
 3) NOTE: PLEASE PROVIDE LIGHTING
 CONTROLS PER FBC 13-415.1.ABC.1.1 AND
 13-415-.1.ABC.1.2 ETC.
 PLEASE PROVIDE SCHEDULING, DEVICES FOR
 OVERRIDES IN AREAS SO THAT THE LIGHTING
 CAN BE SEEN. PLEASE KNOW, NO MORE THAN
 4HRS IS PERMITTED FOR OVER RIDE DEVICES.
 A SPECIFIC SYSTEM SHALL BE SPECIFIED AND
 INDICATED ON PLANS.
 PLEASE SEE AREAS WITH SEPARATE SPACES.
  
 4) NOTE: PLEASE CLARIFY IF THE LOADS
 INDICATED ON PLANS ARE INDEED SHOWN AT
 125% ALREADY FOR CONTINUOUS LOADS, OR
 PLEASE SHOW THE CONTINUOUS LOADS.
 215.3,230.42
  
 5) NOTE: PLEASE BE SURE TO REMOVE OLD/
 VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ** PLEASE SEE PLANS SUBMITTED ARE PLACED
 TOGETHER WITH ONLY ONE STAPLE AND SHOULD
 BE ATTACHED IN A MANNER SO THAT SHEETS
 DO NOT COME APART.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved