| Date |
Text |
| 2006-06-08 00:00:00 | IN REVIEW |
| | ******** UNSAT ******** |
| | |
| | ** PLANS SUBMITTED FOR PERMIT. |
| | |
| | 1) NOTE: PLEASE SEE CIRCUITING FOR |
| | EM/EXT LTS SHALL BE CIRCUITED TO THE |
| | LOCAL BRANCH CIRCUIT LIGHTING IN ANY ONE |
| | AREA. PLEASE SEE A NOTE ON PLANS |
| | MENTIONS TO CIRCUIT TO LOCAL CIRCUIT |
| | AHEAD OF SWITCHING , HOWEVER PLEASE SEE |
| | THESE SEEM TO BE CIRCUITED TO DEDICATED |
| | CIRCUIT(S)? |
| | PLEASE KNOW, IF LIGHTING IN ANY ONE ARE |
| | GOES OUT BY SWITCHING OR TRIPPING A |
| | SINGLE MEANS OF OCP, THE EM LTS SHALL BE |
| | ACTIVATED. THIS WILL ALLEAVIATE ANY ONE |
| | AREA IN DARKNESS. |
| | 700.12E,NFPA-101 7.9.2.2 |
| | |
| | 2) NOTE: PLEASE REFERENCE NFPA-101 2003, |
| | NFPA-72 2002 ON PLANS AS REQUESTED ON |
| | PREVIOUS REVIEW. |
| | |
| | 3) NOTE: PLEASE PROVIDE LIGHTING |
| | CONTROLS PER FBC 13-415.1.ABC.1.1 AND |
| | 13-415-.1.ABC.1.2 ETC. |
| | PLEASE PROVIDE SCHEDULING, DEVICES FOR |
| | OVERRIDES IN AREAS SO THAT THE LIGHTING |
| | CAN BE SEEN. PLEASE KNOW, NO MORE THAN |
| | 4HRS IS PERMITTED FOR OVER RIDE DEVICES. |
| | A SPECIFIC SYSTEM SHALL BE SPECIFIED AND |
| | INDICATED ON PLANS. |
| | PLEASE SEE AREAS WITH SEPARATE SPACES. |
| | |
| | 4) NOTE: PLEASE CLARIFY IF THE LOADS |
| | INDICATED ON PLANS ARE INDEED SHOWN AT |
| | 125% ALREADY FOR CONTINUOUS LOADS, OR |
| | PLEASE SHOW THE CONTINUOUS LOADS. |
| | 215.3,230.42 |
| | |
| | 5) NOTE: PLEASE BE SURE TO REMOVE OLD/ |
| | VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ** PLEASE SEE PLANS SUBMITTED ARE PLACED |
| | TOGETHER WITH ONLY ONE STAPLE AND SHOULD |
| | BE ATTACHED IN A MANNER SO THAT SHEETS |
| | DO NOT COME APART. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |